Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TSU ONE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TSU ONE in 10250 CR 151, KAUFMAN, TX 75142 (NAICS 237130). OSHA activity number 346316433.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch TSU ONE — free Get an email when a new federal OSHA severe-injury report for TSU ONE is published. One employer, no account, unsubscribe in one click.
Establishment
TSU ONE
Site address
10250 CR 151
City
KAUFMAN
State
TX
ZIP
75142
Mailing
3112 WICHITA COURT, FORT WORTH, TX 76140
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
548
Ownership type
A

4 citations on file for this inspection.

1910.269 A02 I A

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 13, 2023
Abate by
Feb 24, 2023
Penalty
Initial $15,625 · Current $11,719 Reduced
29 CFR 1910.269(a)(2)(i)(A):The employer did not ensure that each employee was trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments.  a) On or about October 26, 2022, at a worksite located at 10250 CR 151, Kaufman, TX; where employees, who were working on energized power lines, were not trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to their job assignments, exposing employees to electrocution, electrical shock, and burns.
Recent events (2)
  • — I (S) $11718.75
  • — Z (S) $15625

1910.269 C01 II

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 13, 2023
Abate by
Feb 24, 2023
Penalty
Initial $15,625 · Current $11,719 Reduced
29 CFR 1910.269(c)(1)(ii): The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2), (c)(3), and (c)(4) of this section with the employees involved before they started each job.  a) On or about October 26, 2022, at a worksite located at 10250 CR 151, Kaufman, TX; where employees, who were working on energized power lines, were exposed to electrocution, electrical shock, and burns. The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2), (c)(3), and (c)(4) of this section with the employees involved before the started each job.
Recent events (2)
  • — I (S) $11718.75
  • — Z (S) $15625

1910.269 L01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 13, 2023
Abate by
Feb 24, 2023
Penalty
Initial $15,625 · Current $11,719 Reduced
29 CFR 1910.269(l)(1)(i): Only qualified employees may work on or with exposed energized lines or parts of equipment.  a) On or about October 26, 2022, at a worksite located at 10250 CR 151, Kaufman, TX; where unqualified employees were working on energized power lines, exposing employees to electrocution, electrical shock, and burns.
Recent events (2)
  • — I (S) $11718.75
  • — Z (S) $15625

1910.269 L03 III

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 13, 2023
Abate by
Feb 24, 2023
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless provisions described in (l) (3) (iii) (A) - (C) were followed:   a) The employer did not ensure employees maintained the minimum working distance from energized overhead power lines. This violation occurred on or about October 26, 2022, at a worksite located at 10250 CR 151, Kaufman, TX; where at least one (1) employee, who was working from the electric distribution pole, approached an energized 14.4 kV overhead power line without insulated gloves, and guarding equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $15625

View TSU ONE's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346316433.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.