Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. BORDER PATROL - TUCSON STATION

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of U.S. BORDER PATROL - TUCSON STATION in ATTEN: CHRISTOPHER KOEHLER 2430 S SWAN ROAD, TUCSON, AZ 85711 (NAICS 928120). OSHA activity number 346352248.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Border Patrol - Tucson Station — free Get an email when a new federal OSHA severe-injury report for U.S. Border Patrol - Tucson Station is published. One employer, no account, unsubscribe in one click.
Site address
ATTEN: CHRISTOPHER KOEHLER 2430 S SWAN ROAD
City
TUCSON
State
AZ
ZIP
85711
Mailing
2430 S SWAN ROAD, TUCSON, AZ 85711
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928120
Employees
350
Ownership type
D

2 citations on file for this inspection.

1910.101 B

Serious Gravity 5 1 instance 3 exposed
Issued
Jan 10, 2023
Abate by
Jan 18, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:   a)	BUILDING 3, BAY WEST OF WELDING AREA: Oxygen, Acetylene and LPG cylinders were stored near gasoline and other flammable substances, exposing employees to burns from explosions.
Recent events (1)
  • — Z (S) $0

1910.253 B04 III

Serious Gravity 5 2 instances 3 exposed
Issued
Jan 10, 2023
Abate by
Jan 18, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.253(b)(4)(iii):Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.  a)	BUILDING 3, BAY WEST OF WELDING AREA: Oxygen cylinders were stored 12 feet away from Acetylene cylinders, exposing employees to burns from explosions. b)	BUILDING 3, BAY WEST OF WELDING AREA: Oxygen cylinders were stored with propane cylinders, exposing employees to burns from explosions.