CAMP PENDLETON, CA —
OSHA Inspection: DEFENSE COMMISSARY AGENCY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEFENSE COMMISSARY AGENCY in BLDG 51094 PO BOX 555210, CAMP PENDLETON, CA 92055 (NAICS 445110). OSHA activity number 346355365.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEFENSE COMMISSARY AGENCY
- Site address
- BLDG 51094 PO BOX 555210
- City
- CAMP PENDLETON
- State
- CA
- ZIP
- 92055
- Mailing
- BLDG 51094, CAMP PENDLETON, CA 92055
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 90
- Ownership type
- D
Citations
7 citations on file for this inspection.
1960.8 A
- Issued
- Dec 15, 2022
- Abate by
- May 1, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.8(a): The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm: Warehouse: On and before November 22, 2022, employee(s) were loading/unloading industrial rack system(s). The bases of the industrial rack system(s) were not anchored with anchor bolts to the concrete floor and the industrial rack was missing an under-rack metal brace(s). These conditions potentially exposed employee(s) to rack system(s) tipping over creating crushing hazard(s).
Recent events (1)
- — Z (S) $0
1910.303 G01 II
- Issued
- Dec 15, 2022
- Abate by
- Jan 12, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Warehouse: On and/or before November 22, 2022, employees placed supplies and a 55 gallon trash can in front of electrical panels blocking the access and preventing immediate shutdown of a circuit to the panel in the event of an emergency which exposed employee(s) to electrical and/or fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.305 J02 IV
- Issued
- Dec 15, 2022
- Abate by
- Jan 12, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: Warehouse: Produce Prep Room: On and/or before November 22, 2022, employee(s) accessed the deep sink to clean fresh produce, and, during cleaning operations, water was distributed onto the wall and floor in close proximity to live electrical fixtures which potentially exposed employee(s) to electrical shock hazard(s).
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Dec 15, 2022
- Abate by
- Jan 12, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Warehouse: Produce Prep Room: On and/or before November 22, 2022, employee(s) used the Heat Seal 625A Single 18" Roll Film Axle Mounted Countertop Wrapping Machine to wrap fresh produce for public sale. The outlet was tied into an extension cord cable which was used as fixed wiring which potentially exposed employees to electrical and/or fire hazards.
Recent events (1)
- — Z (S) $0
1910.334 A02 I
- Issued
- Dec 15, 2022
- Abate by
- Jan 12, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): Warehouse: Produce Prep Room: On and/or before November 22, 2022, employee(s) used a Heat Seal 625A Single 18" Roll Film Axle Mounted Countertop Wrapping Machine to wrap fresh produce for public sale. The extension cord used for power had damage to the jacket/insulation exposing the inner wires which potentially exposed employees to electrical shock and/or fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.151 C
- Issued
- Dec 15, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use. Reference: ANSI Z358.1 Emergency Eyewash and Shower Standard 5.4.4 The eyewash unit shall be located on the same level as the hazard and the path of travel shall be free of obstructions that may inhibit the immediate use of the equipment. Battery Charging Area: On and/or before November 22, 2022, employees encountered corrosive materials such as sulfuric acid during forklift battery charging operations and spill cleanup procedures. The plumbed eye wash station next to the charging station was blocked by a Genie GR-20 Vertical Lift and potentially exposed employees to eye burns or blindness.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Dec 15, 2022
- Abate by
- Jan 12, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Warehouse: Administrative Office: On and/or before November 22, 2022, employee(s) used multiple types of office equipment during the assigned duties which were plugged into a relocatable tap which was plugged into an Eaton relocatable tap plugged (daisy chained) into a wall outlet. Employees were potentially exposed to potential fire hazard(s).
Recent events (1)
- — Z (O) $0
More inspections at Defense Commissary Agency
View Defense Commissary Agency's full OSHA safety record →
More inspections in this industry (NAICS 445110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346355365.