MENTOR, OH —
OSHA Inspection: TOM RICHARDS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TOM RICHARDS, INC. in 7010 LINDSAY DRIVE, MENTOR, OH 44060 (NAICS 333249). OSHA activity number 346416092.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TOM RICHARDS, INC.
- Site address
- 7010 LINDSAY DRIVE
- City
- MENTOR
- State
- OH
- ZIP
- 44060
- Mailing
- 7010 LINDSAY DRIVE, MENTOR, OH 44060
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 333249
- Employees
- 165
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.303 G02 I
- Issued
- Jan 24, 2023
- Abate by
- Mar 13, 2023
- Penalty
- Initial $10,046 · Current $5,022 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) On or about January 3, 2023, an employee was exposed to live parts of the TYTAN tankless water heater operating at or below 480-volts during a quality control inspection in the loop area; the employer did not guard the employee against accidental contact of an electrical shock hazard of 480-volts or less by guarding the line side of the control switch located inside of the enclosure.
Recent events (2)
- — I (O) $5022
- — Z (S) $10046
1910.305 B01 I
- Issued
- Jan 24, 2023
- Abate by
- Mar 31, 2023
- Penalty
- Initial $10,046 · Current $5,022 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. a) On or about January 3, 2023, an employee was exposed to a 480-volt electrical shock hazard from unprotected conductors during a quality control inspection of the TYTAN tankless water heater in the loop area; the employer did not ensure that the 3, 1/0 conductors entering a cabinet were protected from abrasion and the opening through which the conductors entered was effectively closed.
Recent events (2)
- — I (O) $5022
- — Z (S) $10046
1910.305 B01 III
- Issued
- Jan 24, 2023
- Abate by
- Mar 13, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(iii): Where cable is used, each cable shall be secured to the cabinet, cutout box, or meter socket enclosure. a) On or about January 3, 2023 employees were exposed to a 480-volt electrical shock hazard from the cable sheath not continuing into the green enclosure during a quality control inspection of the TYTAN tankless water heater in the loop area. The employer did not ensure that the 3 individual 1/0 conductors exiting the top of the green enclosure and the 3 sheathed 1/0 conductors entering the bottom of the green enclosure were protected from abrasion by providing a fitting on each end.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Jan 24, 2023
- Abate by
- Mar 13, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws. a) On or about January 3, 2023, an employee was exposed to a 480-volt electrical shock hazard from the 3, 1/0 flexible cables without strain relief during a quality control inspection of the TYTAN tankless water heater in the loop area; the employer did not ensure that the 3, 1/0 conductors provided strain relief to prevent pull being directly transmitted to the line side of the control switches terminal screws exposing the employees to a 480-volt electrical shock hazard.
Recent events (2)
- — I (O) $0
- — Z (S) $0
More inspections at TOM Richards, INC.
View TOM Richards, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 333249)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346416092.