OSHA Inspection: MCCS OASIS RV PARK AND LODGING

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MCCS OASIS RV PARK AND LODGING in BUILDING 185 AND Q11, BARSTOW, CA 92311 (NAICS 721110). OSHA activity number 346451230.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mccs Oasis RV Park and Lodging — free Get an email when a new federal OSHA severe-injury report for Mccs Oasis RV Park and Lodging is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 185 AND Q11
City
BARSTOW
State
CA
ZIP
92311
Mailing
COMMANDING OFFICER MARINE CORPS LOGISTIC BASE MCCS DIVISION BOX 110600, BARSTOW, CA 92311
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
3
Ownership type
D

2 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 22, 2023
Abate by
Mar 13, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Front Desk Area:  On and/or before January 19, 2023, small appliances such as Keurig Coffeemakers were plugged into relocatable power taps and not used according to listing and labeling instructions. Employee(s) were exposed to potential electrical shock and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 22, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii):  The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Building 185: Cleaning Supply Room:  On and/or before January 19, 2023, electrical panels on the wall was blocked by nonpermanent equipment such as housekeeping carts and supply shelving limiting access by reducing the working space to the panel in cases of emergency shutoff.  This condition exposed employee(s) to electrical and/or fire hazard(s).