OSHA Inspection: CONSOLIDATED EDISON COMPANY OF NEW YORK, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. in CAMPUS ROAD AND HOLSMAN ROAD, STATEN ISLAND, NY 10301 (NAICS 221122). OSHA activity number 346457120.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Consolidated Edison Company of NEW York, INC. — free Get an email when a new federal OSHA severe-injury report for Consolidated Edison Company of NEW York, INC. is published. One employer, no account, unsubscribe in one click.
Site address
CAMPUS ROAD AND HOLSMAN ROAD
City
STATEN ISLAND
State
NY
ZIP
10301
Mailing
4 IRVIN PLACE, 15TH FLOOR, NEW YORK, NY 10003
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
14000
Ownership type
A

4 citations on file for this inspection.

1910.269 L01 III

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jul 14, 2023
Penalty
Initial $15,625 · Current $15,625
29 CFR  1910.269(l)(1)(iii): Electric lines and equipment shall be considered and treated as energized unless they have been deenergized in accordance with paragraph (d) or (m) of this section.   A) Consolidated Edison Co. - Holsman Rd. and Campus Rd., Staten Island NY 10301 - The employer did not ensure the electrical lines and equipment were considered and treated as energized while employees were moving 4KV cables to new utility poles. Employees were exposed to the hazard of electrical shock and burns.   Condition occurred on January 18, 2023.
Recent events (3)
  • — F (O) $15625
  • — C (S) $15625
  • — Z (S) $15625

1910.269 L03 III

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jul 14, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.269(l)(3)(iii): The employer Did Not ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance.   A) Consolidated Edison Co. - Holsman Rd. and Campus Rd., Staten Island NY 10301 - The employer did not ensure during the transfer of energized equipment that employees kept a minimum approach distance of 2' from the electrical lines. Employees exposed to the hazard of electrical shock and burns.   Condition occurred on  January 18, 2023.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.269 M03 I

Serious Gravity 10 1 instance 1 exposed
Issued
Jul 14, 2023
Penalty
Initial $15,625 · Current $15,625
29 CFR  1910.269(m)(3)(i): The employee that the employer designates pursuant to paragraph (m)(2) of this section as being in charge of the clearance shall make a request of the system operator to deenergize the particular section of line or equipment. The designated employee becomes the employee in charge (as this term is used in paragraph (m)(3) of this section) and is responsible for the clearance.  A) Consolidated Edison Co. - Holsman Rd. and Campus Rd., Staten Island NY 10301 - The supervisor did not ensure that section of the electrical lines that was being worked on was deenergized by the Control Center  Operator exposing employees to electrical hazards. Employees were exposed to the hazards of electrical shock and burns.    Condition noted on or about January 18, 2023.
Recent events (3)
  • — F (S) $15625
  • — C (S) $15625
  • — Z (S) $15625

1904.39 A02

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jul 14, 2023
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR  1904.39(a)(2): Basic Requirement. Within twenty-four (24) hours after the in-patient hospitalization of one or more employees or an employee's amputation or an employee's loss of an eye, as a result of a work-related incident, the employer failed to report the in-patient hospitalization, amputation, or loss of an eye to OSHA.  A) Consolidated Edison Co. - Holsman Rd. and Campus Rd., Staten Island NY 10301 - The employer did not report an inpatient hospitalization within 24 hours. A worker sustained injuries due to an electrical shock incident that occurred on January 18, 2023 and was hospitalized the same day. The employer did not report the hospitalization to OSHA until January 24, 2023   Noted on January 24, 2023
Recent events (3)
  • — F (S) $0
  • — C (S) $15625
  • — Z (S) $15625

View Consolidated Edison Company of NEW York, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346457120.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.