Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ANGEL OF THE WINDS CASINO RESORT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ANGEL OF THE WINDS CASINO RESORT in 3438 STOLUCKQUAMISH LANE, ARLINGTON, WA 98223 (NAICS 721120). OSHA activity number 346470321.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Angel of the Winds Casino Resort — free Get an email when a new federal OSHA severe-injury report for Angel of the Winds Casino Resort is published. One employer, no account, unsubscribe in one click.
Site address
3438 STOLUCKQUAMISH LANE
City
ARLINGTON
State
WA
ZIP
98223
Mailing
3438 STOLUCKQUAMISH LANE, ARLINGTON, WA 98223
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721120
Employees
720
Ownership type
A

8 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 1 instance 720 exposed
Issued
Mar 13, 2023
Abate by
Apr 6, 2023
Penalty
Initial $5,692 · Current $3,415 Reduced
29 CFR 1910.36(g)(2): An exit access was not at least 28 inches (71.1 cm) wide at all points:  a) The Grind Coffee Caf�, where the configuration of the built-in counter and ice cream freezer reduced the exit access width to 26 inches.
Recent events (2)
  • — I (S) $3415.2
  • — Z (S) $5692

1910.37 A03

Serious Gravity 1 2 instances 720 exposed
Issued
Mar 13, 2023
Abate by
Apr 6, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit routes were not kept free and unobstructed:  a) Facility, where items were stored in the exit route.  1. W?l�?ali Hall, the banquet hall exit route was used to store tables, chairs stage platforms, wood pallets, and a pallet jack.  2. Katie's Kitchen, the kitchen's exit route was used to hold two large refrigerators on wheels, mop equipment, and a bucket.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B02

Serious Gravity 1 4 instances 720 exposed
Issued
Mar 13, 2023
Abate by
Apr 6, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  a) Facility, where the designated emergency exit doors not equipped with exit signs included:  1. EVS Warehouse, door that opened into the exit access hallway.  2. Boiler Room Office, door that opened into the exit access.  3. Chiller Room, exit discharge door.  4. Jade 210 Kitchen, door that opened into the exit access stairwell.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B05

Serious Gravity 1 1 instance 720 exposed
Issued
Mar 13, 2023
Abate by
Apr 6, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or identified by a sign indicating its actual use (e.g. closet):  a) Hotel Laundry Room, where doors to the Dryer Maintenance Room and Boiler room that led to dead-ends did not have signs.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 720 exposed
Issued
Mar 13, 2023
Abate by
Apr 6, 2023
Penalty
Initial $5,692 · Current $3,415 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) Slots Repair Management Office, where two relocatable power taps were daisy chained and used to supply power to the Frigidaire refrigerator and the microwave.
Recent events (2)
  • — I (S) $3415.2
  • — Z (S) $5692

1910.305 B02 I

Serious Gravity 1 3 instances 720 exposed
Issued
Mar 13, 2023
Abate by
Apr 6, 2023
Penalty
Initial $5,692 · Current $3,415 Reduced
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a) Facility, where outlets not equipped with face plates included, but were not limited to:  1. Strikerz Bowling Alley Maintenance Shop, the outlet used to supply power to the extension cord that energized the Avanti refrigerator and the Bella air fryer (item corrected).  2. Katie's Kitchen Hallway, three outlets not equipped with covers used to supply power to the cigarette vending machine and two portable fans.  3. Employee Break Room Hallway, an outlet that was available for use.
Recent events (2)
  • — I (S) $3415.2
  • — Z (S) $5692

1910.305 G01 IV A

Serious Gravity 1 4 instances 720 exposed
Issued
Mar 13, 2023
Abate by
Apr 6, 2023
Penalty
Initial $5,692 · Current $3,415 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Facility, where flexible cords and cables were used as a substitute for fixed wiring, included:    1. Strikerz Bowling Alley Maintenance Shop, where an orange and black extension cord was used to supply power to the Avanti refrigerator and Bella air fryer located in the shop.   2. Environmental Specialist (EVS) Warehouse cubicle, where a yellow extension cord was used to supply power to a microwave (item corrected).  3. Employee Break Room Hallway, where an orange extension cord was used to supply power to the commercial refrigerator.  4. Employee Break Room Area, where a yellow extension cord was used to supply power to the commercial refrigerator.
Recent events (2)
  • — I (S) $3415.2
  • — Z (S) $5692

1910.147 C04 I

Other-than-serious 1 instance 720 exposed
Issued
Mar 13, 2023
Abate by
Apr 6, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:   a) Maintenance Department, where the employer utilized the lockout tagout program for safe electrical work practices, no written procedures were developed for preventative maintenance and repair of the HVAC system.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Angel of the Winds Casino Resort's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346470321.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.