Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HEART AUTOMOTIVE LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HEART AUTOMOTIVE LLC in 1557 YARROW STREET, LAKEWOOD, CO 80214 (NAICS 811111). OSHA activity number 346486491.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Heart Automotive LLC — free Get an email when a new federal OSHA severe-injury report for Heart Automotive LLC is published. One employer, no account, unsubscribe in one click.
Site address
1557 YARROW STREET
City
LAKEWOOD
State
CO
ZIP
80214
Mailing
7801 W COLFAX AVE, LAKEWOOD, CO 80214
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811111
Employees
2
Ownership type
A

6 citations on file for this inspection.

1910.215 A04

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 2, 2023
Abate by
Mar 28, 2023
Penalty
Initial $4,687 · Current $2,344 Reduced
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  (a) On or before 2/7/23, the employer did not ensure that the work rest on the Bauer bench grinder was adjusted to no more than 1/8th of an inch maximum opening. This condition exposed employees to ingoing nip points and flying chips and sparks.
Recent events (2)
  • — I (S) $2343.5
  • — Z (S) $4687

1910.303 G01 II

Serious Gravity 1 1 instance 3 exposed
Issued
Mar 2, 2023
Abate by
Mar 28, 2023
Penalty
Initial $4,687 · Current $2,344 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  (a) On or before 2/7/23, the employer did not ensure that service panels rated 600 Volts or less had at least 30 inches of clearance. The area in front of the service panels had items stored within 30 inches of the panel. This condition exposed employees to electric shock and fire hazards.
Recent events (2)
  • — I (S) $2343.5
  • — Z (S) $4687

1910.303 G02 I

Serious Gravity 1 1 instance 3 exposed
Issued
Mar 2, 2023
Abate by
Mar 28, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  (a) On or before 2/7/23, the employer did not ensure that the dead front of a live service panel was installed. This condition exposed employees to electric shock and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 3 exposed
Issued
Mar 2, 2023
Abate by
Mar 28, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  (a) On or before 2/7/23, the employer did not ensure that all electrical junction boxes and fittings were provided with covers. Electrical outlets and switches lacked covers throughout the automotive building. This condition exposed employees to electric shock and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B02

Other-than-serious 1 instance 3 exposed
Issued
Mar 2, 2023
Abate by
Mar 28, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  (a) On or before 2/7/23, the employer did not ensure that all exits were marked in accordance with this standard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E03

Other-than-serious 1 instance 3 exposed
Issued
Mar 2, 2023
Abate by
Mar 28, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:   (a) On or before 2/7/23, the employer did not ensure that all portable fire extinguishers were subjected to an annual maintenance check. Fire extinguishers were overdue for their annual maintenance checks. This condition exposed employees to fire hazards.