OSHA Inspection: PUBLIC SERVICE COMPANY OF OKLAHOMA

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of PUBLIC SERVICE COMPANY OF OKLAHOMA in 4228 E. 103RD, TULSA, OK 74137 (NAICS 221118). OSHA activity number 346590284.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Public Service Company of Oklahoma — free Get an email when a new federal OSHA severe-injury report for Public Service Company of Oklahoma is published. One employer, no account, unsubscribe in one click.
Site address
4228 E. 103RD
City
TULSA
State
OK
ZIP
74137
Mailing
5524 EAST 15TH STREET, TULSA, OK 74112
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221118
Employees
1035
Ownership type
A

5 citations on file for this inspection.

1910.269 A04

Serious Gravity 10 1 instance 2 exposed
Issued
Sep 13, 2023
Abate by
Oct 2, 2023
Penalty
Initial $15,625 · Current $15,625
29 CFR 1910.269(a)(4):  Existing characteristics and conditions of electric lines and equipment that were related to the safety of the work to be performed was not determined before work on or near the lines or equipment was started:    On or about March 22, 2023, at a remote location behind a personal residence, the existing condition of a transformer was not determined and communicated, exposing employees and contract employees to the hazard of coming in contact with energized parts.
Recent events (2)
  • — I (S) $15625
  • — Z (S) $15625

1910.269 D03 II F

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Sep 13, 2023
Abate by
Oct 2, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.269(d)(3)(ii)(F): Tagout devices did not  warn against hazardous conditions of energized machines or equipment:  On or about March 22, 2023, at a remote location behind a personal residence, employees used hold cards that had the incorrect information about the condition of the transformer and lines, exposing employees and employees of a contractor to the hazard of coming in contact with energized parts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 N02 I

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Sep 13, 2023
Abate by
Oct 2, 2023
Penalty
Initial $15,625 · Current $15,625
29 CFR 1910.269(n)(2)(i):  Lines and equipment were not deenergized according to the provisions of paragraph (m) of this section:    On or about March 22, 2023, at a remote location behind a personal residence, energized lines in a transformer were not deenergized prior to work commencing, exposing employees and contract employees to the hazard of coming in contact with energized parts.
Recent events (2)
  • — I (O) $15625
  • — Z (S) $15625

1910.269 N06 I

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Sep 13, 2023
Abate by
Oct 2, 2023
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR 1910.269(n)(6)(i): Employees were allowed to attach the testing end of grounding cables without attaching the ground-end connection first:  On or about March 22, 2023, at a remote location in the backyard of a personal residence, while connecting the cables of fault locator to the cables in a transformer, the employee at the transformer contacted the cables in the transformer before the employee on the opposite end attached the ground cable, exposing employees and contract employees  to the hazard of coming in contact with energized/ungrounded parts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $15625

1910.269 O02 I

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Sep 13, 2023
Abate by
Oct 2, 2023
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR  1910.269(o)(2)(i): Work practices for the protection of each worker was not established from the hazards of high-voltage or high-power testing at all test areas, temporary and permanent:  On or about March 22, 2023, at a remote location, employees opened and began to work on the internal parts of a transformers without testing the wiring to ensure the system was de-energized, exposing employees to the hazard of coming in contact with energized parts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $15625

View Public Service Company of Oklahoma's full OSHA safety record →