MARTINS FERRY, OH —
OSHA Inspection: AUSTIN MASTER SERVICES, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of AUSTIN MASTER SERVICES, LLC in 1097 NORTH 1ST STREET, MARTINS FERRY, OH 43935 (NAICS 213112). OSHA activity number 346610801.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AUSTIN MASTER SERVICES, LLC
- Site address
- 1097 NORTH 1ST STREET
- City
- MARTINS FERRY
- State
- OH
- ZIP
- 43935
- Mailing
- 6000 TOWNCENTER BLVD, SUITE 210, CANONSBURG, PA 15317
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213112
- Employees
- 30
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.303 B01 IV
- Issued
- Jun 9, 2023
- Abate by
- Jun 21, 2023
- Penalty
- Initial $7,813 · Current $7,813
General-duty citation text
29 CFR 1910.303(b)(1):Examination. Electric equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment shall be determined using the following considerations: 29 CFR 1910.303(b)(1)(iv): Electrical insulation; a. On or about March 4, 2023, the employer failed to remove a space heater from service that had a exposed damaged cord, thereby exposing employees to electrical shock and/or fire hazards.
Recent events (2)
- — I (S) $7813
- — Z (S) $7813
1910.303 B02
- Issued
- Jun 9, 2023
- Abate by
- Jun 21, 2023
- Penalty
- Initial $7,813 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2):Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. a. On or about March 4, 2023, two 120 VAC extension cords were daisy chained together to energize a space heater in the press area. The cord was being utilized outside its approved use.
Recent events (2)
- — I (S) $0
- — Z (S) $7813
1910.303 G02 I
- Issued
- Jun 9, 2023
- Abate by
- Jun 21, 2023
- Penalty
- Initial $7,813 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as�elsewhere required�or permitted�by this�standard, live�parts of�electric equipment�operating at�50 volts�or more�shall be�guarded against�accidental contact by�use of�approved cabinets�or other�forms of�approved enclosures�or by�any of�the following�means: a. On or about March 4, 2023, the employer had exposed 120VAC electrical wires located under the electrical disconnects in the agitator area, thereby exposing employees to electrical shock hazards. b. On or about March 4, 2023, the employer had exposed 120VAC electrical wires dangling from a conduit approximately 5 feet from the floor attached to the overhead mezzanine in the clean out area below the presses, thereby exposing employees to electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $7813
1910.305 G01 IV A
- Issued
- Jun 9, 2023
- Abate by
- Jun 21, 2023
- Penalty
- Initial $7,813 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv):Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: 29 CFR 1910.305(g)(1)(iv)(A): As a substitute for the fixed wiring of a structure; a. On or about March 4, 2023, two extension cords were being used to provide 120 VAC to a space heater located in the press area. The cords were being used in lieu of fixed wiring, thereby exposing employees to electrical shock and/or fire hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $7813
1910.305 G01 IV D
- Issued
- Jun 9, 2023
- Abate by
- Jun 21, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv):Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: 29 CFR 1910.305(g)(1)(iv)(D): Where attached to building surfaces; a. On or about March 4, 2023, a 120 VAC extension cord was fastened to the press area mezzanine structure using zip ties which provided electric to equipment in use, such as a space heater. The condition exposed employees to electrical shock and/or fire hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Austin Master Services, LLC
View Austin Master Services, LLC's full OSHA safety record →
More inspections in this industry (NAICS 213112)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346610801.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.