TULSA, OK —
OSHA Inspection: PROFESSIONAL FABRICATORS INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PROFESSIONAL FABRICATORS INC in 2765 DAWSON ROAD, TULSA, OK 74110 (NAICS 332312). OSHA activity number 346640741.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PROFESSIONAL FABRICATORS INC
- Site address
- 2765 DAWSON ROAD
- City
- TULSA
- State
- OK
- ZIP
- 74110
- Mailing
- 2765 DAWSON ROAD, TULSA, OK 74110
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332312
- Employees
- 31
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.253 B04 III
- Issued
- Oct 11, 2023
- Abate by
- Oct 30, 2023
- Penalty
- Initial $6,250 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m): The employer does not ensure compress gas cylinders of oxygen and acetylene were stored at least 20' apart, exposing employees to fire and explosion hazards. a) This violation was observed on or about April 17, 2023, where compressed gas cylinders of oxygen and acetylene were observed with gauges still on and according to employees, not used within 24 hours. Cylinders located on east wall of facility in middle of shop. b) This violation was observed on or about April 17, 2023, where compressed gas cylinders of oxygen and propane were observed with gauges still on and according to employees, not used within 24 hours. A small cylinder of acetylene was also located with the other cylinder. Cylinders located on east wall of facility in middle of shop. c) This violation was observed on or about April 17, 2023, where compressed gas cylinders of oxygen and acetylene were observed with gauges still on and according to employees, not used within 24 hours. Cylinders located on east wall of facility in middle of shop. d) This violation was observed on or about April 17, 2023, where compressed gas cylinders of oxygen and acetylene were observed with gauges still on and according to employees, not used within 24 hours. Cylinders located on east wall of facility in middle of shop. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps taken to ensure oxygen and propylene cylinders are stored at least 20' apart.
Recent events (2)
- — I (S) $5000
- — Z (S) $6250
1910.305 B01 II
- Issued
- Oct 11, 2023
- Abate by
- Oct 30, 2023
- Penalty
- Initial $7,813 · Current $6,000 Reduced
General-duty citation text
1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed: The employer does not ensure that unused openings in electrical disconnect panels are effectively closed, this violation was observed on or about April 17, 2023, where a 4-way outlet pendant box was missing a pre-punched knockout. The pendant box was located on the west wall in the facility, exposing employees to electrical hazards. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps taken to ensure that unused openings in cabinets, boxes, and fittings are effectively closed.
Recent events (2)
- — I (S) $6000
- — Z (S) $7813
1910.303 B02
- Issued
- Oct 11, 2023
- Abate by
- Oct 30, 2023
- Penalty
- Initial $6,250 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not used or installed in accordance with any instructions included in the listing or labeling: The employer does not ensure relocatable power taps are not secured to the structure, exposing employees to electricals hazards. a) This violation was observed on or about April 17, 2023, where a relocatable power tap was observed attached/hanging from mounted objects the structure walls. The relocatable power tap was located in a welding booth along the east walls in the middle of the facility. b) This violation was observed on or about April 17, 2023, where a relocatable power tap was observed attached/hanging from mounted objects the structure walls. The relocatable power tap was located in a welding booth along the east walls in the middle of the facility. c) This violation was observed on or about April 17, 2023, where a relocatable power tap was observed attached/hanging from mounted objects the structure walls. The relocatable power tap was located in a welding booth along the east walls in the middle of the facility. d) This violation was observed on or about April 17, 2023, where a relocatable power tap was observed attached/hanging from mounted objects the structure walls. The relocatable power tap was located in a welding booth along the east walls in the middle of the facility. e) This violation was observed on or about April 17, 2023, where a relocatable power tap was observed attached/hanging from mounted objects the structure walls. The relocatable power tap was located in a welding booth along the east walls in the middle of the facility. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps taken to ensure electrical equipment is being used in accordance with their intended use.
Recent events (2)
- — I (S) $0
- — Z (S) $6250
1910.303 G01
- Issued
- Oct 11, 2023
- Abate by
- Oct 30, 2023
- Penalty
- Initial $6,250 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: The employer does not ensure working space is maintained around 600-volt panels by allowing product and other materials to be stored in front of the panels, exposing employees to shock hazards. a) This violation was observed on or about April 17, 2023, where a 480-volt panel was blocked by a double stacked toolbox. The panel located on the north side of the shop. b) This violation was observed on or about April 17, 2023, where a 480-volt panel was blocked by product and other equipment in the shop. The panel located on the north side of the shop. Pursuant to 29 CFR 1903.19, within (10) calendar days of the date of this citation, the employer must submit documentation describing the steps taken to ensure sufficient access and working is provided and maintained about all electric equipment operating at 600 volts, nominal, or less to ground.
Recent events (2)
- — I (S) $0
- — Z (S) $6250
1910.305 G01 IV A
- Issued
- Oct 11, 2023
- Abate by
- Oct 30, 2023
- Penalty
- Initial $7,813 · Current $6,000 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: The employer does not ensure that extension cords (flexible wiring) are not used as a substitute for fixed wiring, exposing employees to electrical hazards. a) This hazard was observed on or about April 17, 2023, where an extension cord was wrapped around beams and other parts of the structure. The flexible cord used as permanent wiring was observed in a paint booth along the west wall in the middle of the facility. b) This hazard was observed on or about April 17, 2023, where an extension cord was wrapped around beams and other parts of the structure. The flexible cord used as permanent wiring was observed in a paint booth along the east wall in the middle of the facility. c) This hazard was observed on or about April 17, 2023, where an extension cord was wrapped around beams and other parts of the structure. The flexible cord used as permanent wiring was observed in a paint booth along the east wall in the middle of the facility. d) This hazard was observed on or about April 17, 2023, where an extension cord was wrapped around beams and other parts of the structure. The flexible cord used as permanent wiring was observed in a paint booth along the west wall in the middle of the facility. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps taken to ensure that all flexible cords and/or cables are not used as a substitute for fixed wiring.
Recent events (2)
- — I (S) $6000
- — Z (S) $7813
1910.305 G01 IV B
- Issued
- Oct 11, 2023
- Abate by
- Oct 30, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: The employer does not ensure that flexible cords are not ran through holes in walls, this violation was observed on or about April 17, 2023, where a extension cord was ran through a hole in the wall at the facility, the cord in the wall was located on the east side wall in the north end of the shop, exposing employees to electrical hazards. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the steps taken to ensure that flexible are not ran through holes in the walls.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Professional Fabricators INC
View Professional Fabricators INC's full OSHA safety record →
More inspections in this industry (NAICS 332312)
More inspections in OK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346640741.