Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AMSPEC ST. CROIX, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AMSPEC ST. CROIX, LLC in 9010 ESTATE COTTAGE SUITE 3, CHRISTIANSTED, VI 00820 (NAICS 541380). OSHA activity number 346680226.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Amspec ST. Croix, LLC — free Get an email when a new federal OSHA severe-injury report for Amspec ST. Croix, LLC is published. One employer, no account, unsubscribe in one click.
Site address
9010 ESTATE COTTAGE SUITE 3
City
CHRISTIANSTED
State
VI
ZIP
00820
Mailing
9010 ESTATE COTTAGE SUITE 3, CHRISTIANSTED, VI 00820
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541380
Employees
25
Ownership type
A

5 citations on file for this inspection.

1910.37 A03

Serious Gravity 1 1 instance 56 exposed
Issued
Jul 12, 2023
Penalty
Initial $3,984 · Current $2,590 Reduced

Hazardous substances 13402150

29 CFR 1910.37(a)(3): Exit routes were not kept free and unobstructed.  Materials or equipment were placed, either permanently or temporarily, within the exit route.  On or about 24 April 2023, at the  back exit door, AmSpec St. Croix location; the egress route and access to an emergency exit door was obstructed by metal railings, a fuel canister and a 25-lb propane metal tank.  NOTE: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer during the inspection.
Recent events (2)
  • — I (S) $2589.6
  • — Z (S) $3984

1910.37 B02

Serious Gravity 1 1 instance 56 exposed
Issued
Jul 12, 2023
Abate by
Jul 26, 2023
Penalty
Initial $3,984 · Current $2,590 Reduced

Hazardous substances 13402150D150

29 CFR  1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "EXIT":  On or about 24 April 2023, at the AmSpec St. Croix location, towards the rear exit next to the QA laboratory, a designated exit was not marked by an exit sign or any other means.   NOTE: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer during the inspection.
Recent events (2)
  • — I (S) $2589.6
  • — Z (S) $3984

1910.106 D05 III

Serious Gravity 5 1 instance 35 exposed
Issued
Jul 12, 2023
Penalty
Initial $6,641 · Current $4,317 Reduced

Hazardous substances 0080X100

29 CFR  1910.106(d)(5)(iii): Flammable liquid storage in office occupancies was not prohibited except that which is required for maintenance and operation of building and operation of equipment.    On or about 24 April 2023, at the enclosed storage area in the back of the building, AmSpec testing laboratories and offices, St. Croix, VI, several 55-gal drums containing a flammable liquid (diesel) co-located next to several oxygen, hydrogen and acetylene cylinders were storage inside in the back of the building.  NOTE: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer during the inspection.
Recent events (2)
  • — I (S) $4316.65
  • — Z (S) $6641

1910.106 D07 III

Serious Gravity 1 1 instance 35 exposed
Issued
Jul 12, 2023
Penalty
Initial $3,984 · Current $2,590 Reduced

Hazardous substances 0080X100

29 CFR  1910.106(d)(7)(iii): Open flames and smoking were not permitted in flammable or combustible liquid storage areas:   On or about 24 April 2023, at the AmSpec testing laboratories and offices, St. Croix, VI.   In an enclosed area where several oxygen, hydrogen and acetylene cylinders where located in the same vicinity of several flammable 55-gall drums of diesel, a minimum of one "No-Smoking" sign was not posted or accessible to employees to prevent them from smoking within the premises.    NOTE: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer during the inspection.
Recent events (2)
  • — I (S) $2589.6
  • — Z (S) $3984

1910.157 C01

Other-than-serious 1 instance 35 exposed
Issued
Jul 12, 2023
Abate by
Jul 21, 2023
Penalty
Initial $0 · Current $0

Hazardous substances 0080X100

29 CFR  1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:   On or about 24 April 2023, at the AmSpec testing laboratories and offices, St. Croix, VI.   In an enclosed area where several oxygen, hydrogen and acetylene cylinders where located in the same vicinity of several flammable 55-gall drums of diesel, a minimum of one regulated portable fire extinguisher was not provided or accessible to employees in case of a fire emergency.  NOTE:	Certification of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Amspec ST. Croix, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346680226.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.