Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ULTIUM CELLS LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of ULTIUM CELLS LLC in 7400 TOD AVENUE SOUTHWEST, WARREN, OH 44481 (NAICS 335912). OSHA activity number 346805054.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ultium Cells LLC — free Get an email when a new federal OSHA severe-injury report for Ultium Cells LLC is published. One employer, no account, unsubscribe in one click.
Establishment
ULTIUM CELLS LLC
Site address
7400 TOD AVENUE SOUTHWEST
City
WARREN
State
OH
ZIP
44481
Mailing
7400 TOD AVENUE SOUTHWEST, WARREN, OH 44481
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
335912
Employees
1200
Ownership type
A

4 citations on file for this inspection.

1910.165 D01

Deleted Serious Gravity 10 1 instance 80 exposed
Issued
Dec 12, 2023
Abate by
Jan 9, 2024
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR  1910.165(d)(1): Employee alarm systems were not maintained in operating condition:  On or about June 27, 2023, the alarm system in Area 400 of the facility, including degas, was bypassed due to construction in a different part of Area 400. A fire occurred on degas line 3-2, and employees were not immediately informed to evacuate.
Recent events (3)
  • — F (S) $0
  • — C (S) $15625
  • — Z (S) $15625

1910.307 B

Deleted Serious Gravity 10 1 instance 20 exposed
Issued
Dec 12, 2023
Abate by
Jan 31, 2024
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR  1910.307(b): Areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007 were not properly documented:  On or about June 29, 2023, the employer failed to document areas designated as hazardous locations in the degas area of the facility, including but not limited to line 3-2, when electrolyte, which is a flammable liquid that produces flammable vapors, is handled near electrical components.
Recent events (3)
  • — F (S) $0
  • — C (S) $15625
  • — Z (S) $15625

1910.307 C03

Deleted Serious Gravity 10 1 instance 20 exposed
Issued
Dec 12, 2023
Abate by
Jan 31, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.307(c)(3): Equipment was not safe for the location in that it was not of a type and design that the employer demonstrated would provide protection from the hazards arising from the combustibility and flammability of vapors, liquids, gases, dusts, or fibers involved:   On or about June 27, 2023, the employer did not demonstrate that the electrical equipment present on the degas lines, including but not limited to line 3-2, was safe for the location in that it would provide protection from the hazards arising from the combustibility and flammability of vapors, liquids, and gases when exposed to electrolyte, which is a flammable liquid that produces flammable vapors.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1904.39 A02

Other-than-serious 2 instances 2 exposed
Issued
Dec 12, 2023
Penalty
Initial $11,162 · Current $5,500 Reduced
29 CFR  1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye:  a. On or about June 27, 2023, an employee was admitted to the hospital and received medical treatment due to smoke inhalation from a fire on line 3-2 in degas. The employee worked to extinguish the fire. The employer failed to report the hospitalization to OSHA.
Recent events (3)
  • — F (O) $5500
  • — C (O) $11162
  • — Z (O) $11162

View Ultium Cells LLC's full OSHA safety record →