Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NATIONAL PARK SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE in BUILDING 164, DENALI NATIONAL PARK, AK 99755 (NAICS 811198). OSHA activity number 346845902.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service — free Get an email when a new federal OSHA severe-injury report for National Park Service is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 164
City
DENALI NATIONAL PARK
State
AK
ZIP
99755
Mailing
P.O. BOX 9, DENALI NATIONAL PARK, AK 99755
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811198
Employees
10
Ownership type
D

12 citations on file for this inspection.

1910.36 D01

Serious Gravity 1 1 instance 9 exposed
Issued
Jan 10, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.36(d)(1):  Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge.  a) Weld Shop:  On or about July 18, 2023,  the emergency exit in the back of the welding area was locked with a deadbolt at the top of the door preventing employees from opening the door, exposing them to delayed egress and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.37 A03

Serious Gravity 1 1 instance 9 exposed
Issued
Jan 10, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.37(a)(3):  Exit route(s) were not kept free and unobstructed.  a) Weld Shop:  On or about July 18, 2023, the emergency exit in the back of the welding area was blocked with a large piece of machinery, exposing employees to a delayed egress and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.184 D

Serious Gravity 5 1 instance 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.184(d):  Each day before being used, the sling and all fastenings and attachments were not being inspected for damage or defects by a competent person designated by the employer.  a) On or about July 18, 2023, a competent person was not designated to inspect all slings, alloy steel chains and synthetic slings, throughout the auto shop exposing employees to struck by hazards.
Recent events (1)
  • — Z (S) $0

1910.184 E01

Serious Gravity 5 1 instance 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.184(e)(1):  Alloy steel sling(s) did not have permanently affixed durable identification stating size, grade, rated capacity, and reach.  a) On or about July 18, 2023, alloy steel chain slings used in the auto shop did have a permanently affixed identification tag exposing employees to struck by hazards.
Recent events (1)
  • — Z (S) $0

1910.184 E03 I

Serious Gravity 5 1 instance 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.184(e)(3)(i):  A thorough periodic inspection of alloy steel chain slings was not made on a regular basis and/or were done at intervals greater than once every 12 months.  a) On or about July 18, 2023, alloy steel chain slings used in the auto shop did not have periodic inspections completed exposing employees to struck by hazard.
Recent events (1)
  • — Z (S) $0

1910.184 E03 II

Serious Gravity 5 1 instance 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.184(e)(3)(ii):  Records of the most recent month in which each alloy steel chain sling was thoroughly inspected were not available for examination.  a) On or about July 18, 2023, alloy steel chain slings used in the auto shop did not have inspection records for the last month, exposing employees to struck by hazards.
Recent events (1)
  • — Z (S) $0

1910.184 E04

Serious Gravity 5 1 instance 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.184(e)(4): Certificate(s) of proof test were not available for new, repaired or reconditioned alloy steel chain slings.  a) On or about July 18, 2023, alloy steel chain slings used in the auto shop did not have certificates of proof test, exposing employees to struck by hazards.
Recent events (1)
  • — Z (S) $0

1910.212 A01

Serious Gravity 5 1 instance 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(1):  One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks.  a) On or about July 18, 2023, a Goodway metal lathe, model number GW-1660, does not have a guard covering the lathe chuck component of the machine, exposing employees to a caught-in and amputation hazard.
Recent events (1)
  • — Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1):  Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment.  a) On or about July 18, 2023, three hazardous materials containers were stored in front of two electrical panels restricting the working space and did not allow the panel accessible in the event of an emergency, exposing employees to electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i):  Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:   a) On or about July 18, 2023, the enclosure cover on two metal junction boxes were removed and the live parts were exposed, exposing employees to electrical and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Other-than-serious 2 instances 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):  Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.  a) On or about July 18, 2023, two fire extinguishers were mounted on the buildings center beams and were blocked by hoses and extensions cords exposing employees to a fire hazard.
Recent events (1)
  • — Z (O) $0

1910.303 B02

Other-than-serious 2 instances 9 exposed
Issued
Jan 10, 2024
Abate by
Jan 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  a) On or about July 18, 2023, the door to an energized electrical panel D  was not closed, exposing employees to electrical hazard.  b) On or about July 18, 2023, the door to an energized electrical panel C  was not closed, exposing employees to electrical hazard.
Recent events (1)
  • — Z (O) $0

View National Park Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346845902.