OSHA Inspection: BUREAU OF INDIAN AFFAIRS - T'IIS NAZBAS COMMUNITY SCHOOL

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUREAU OF INDIAN AFFAIRS - T'IIS NAZBAS COMMUNITY SCHOOL in HWY 160 BIA RD N #5114, TEEC NOS POS, AZ 86514 (NAICS 611110). OSHA activity number 346847064.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bureau of Indian Affairs - T'Iis Nazbas Community School — free Get an email when a new federal OSHA severe-injury report for Bureau of Indian Affairs - T'Iis Nazbas Community School is published. One employer, no account, unsubscribe in one click.
Site address
HWY 160 BIA RD N #5114
City
TEEC NOS POS
State
AZ
ZIP
86514
Mailing
PO BOX 2002, TEEC NOS POS, AZ 86514
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
611110
Employees
33
Ownership type
D

6 citations on file for this inspection.

1910.212 B

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 11, 2023
Abate by
Sep 18, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.212(b):Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:  MAINTENANCE SHOP - Bench Grinder not secured to the floor or workbench, exposing employees to struck-by and caught-in hazards.
Recent events (1)
  • — Z (S) $0

1910.215 A04

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 11, 2023
Abate by
Sep 18, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.215(a)(4):Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  MAINTENANCE SHOP - Bench Grinder tool rest not properly adjusted (should be 1/8" or less), exposing employees to caught-in hazards.
Recent events (1)
  • — Z (S) $0

1910.253 B02 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 11, 2023
Abate by
Sep 18, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.253(b)(2)(iv):Valve protection caps, where cylinders were designed to accept caps, were not always in place, hand-tight, except when cylinders were in use or connected for use:  Maintenance Shop - Oxygen and Acetylene compressed gas bottles stored with welding gauges attached and without protective caps exposing employees to projectile hazards.
Recent events (1)
  • — Z (S) $0

1910.253 B04 III

Serious Gravity 10 1 instance 2 exposed
Issued
Sep 11, 2023
Abate by
Sep 18, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.  MAINTENENCE SHOP: Oxygen cylinder and Acetylene cylinder stored adjacent on welding cart with no fire resistance separation subjecting employees to fire hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Sep 11, 2023
Abate by
Sep 28, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(2)(i):Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  BOILER ROOM: The electrical panel face had been removed leaving live 240AC / 600A bus bars unguarded, exposing employees to electrocution hazards.
Recent events (1)
  • — Z (S) $0

1910.304 F01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Sep 11, 2023
Abate by
Sep 28, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.304(f)(1)(i): Conductors and equipment were not protected from overcurrent in accordance with their ability to safely conduct current:  BOILER ROOM: The electrical panel (240AC / 600A) had 3/0 copper wire (approximately 200 Amp capacity) coming of the 600A bus bars to a secondary box, exposing employees to electrical and fire hazards.
Recent events (1)
  • — Z (S) $0

View Bureau of Indian Affairs - T'Iis Nazbas Community School's full OSHA safety record →