TEEC NOS POS, AZ —
OSHA Inspection: BUREAU OF INDIAN AFFAIRS - T'IIS NAZBAS COMMUNITY SCHOOL
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUREAU OF INDIAN AFFAIRS - T'IIS NAZBAS COMMUNITY SCHOOL in HWY 160 BIA RD N #5114, TEEC NOS POS, AZ 86514 (NAICS 611110). OSHA activity number 346847064.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- HWY 160 BIA RD N #5114
- City
- TEEC NOS POS
- State
- AZ
- ZIP
- 86514
- Mailing
- PO BOX 2002, TEEC NOS POS, AZ 86514
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 611110
- Employees
- 33
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.212 B
- Issued
- Sep 11, 2023
- Abate by
- Sep 18, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b):Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving: MAINTENANCE SHOP - Bench Grinder not secured to the floor or workbench, exposing employees to struck-by and caught-in hazards.
Recent events (1)
- — Z (S) $0
1910.215 A04
- Issued
- Sep 11, 2023
- Abate by
- Sep 18, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4):Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch: MAINTENANCE SHOP - Bench Grinder tool rest not properly adjusted (should be 1/8" or less), exposing employees to caught-in hazards.
Recent events (1)
- — Z (S) $0
1910.253 B02 IV
- Issued
- Sep 11, 2023
- Abate by
- Sep 18, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(2)(iv):Valve protection caps, where cylinders were designed to accept caps, were not always in place, hand-tight, except when cylinders were in use or connected for use: Maintenance Shop - Oxygen and Acetylene compressed gas bottles stored with welding gauges attached and without protective caps exposing employees to projectile hazards.
Recent events (1)
- — Z (S) $0
1910.253 B04 III
- Issued
- Sep 11, 2023
- Abate by
- Sep 18, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour. MAINTENENCE SHOP: Oxygen cylinder and Acetylene cylinder stored adjacent on welding cart with no fire resistance separation subjecting employees to fire hazards.
Recent events (1)
- — Z (S) $0
1910.303 G02 I
- Issued
- Sep 11, 2023
- Abate by
- Sep 28, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i):Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): BOILER ROOM: The electrical panel face had been removed leaving live 240AC / 600A bus bars unguarded, exposing employees to electrocution hazards.
Recent events (1)
- — Z (S) $0
1910.304 F01 I
- Issued
- Sep 11, 2023
- Abate by
- Sep 28, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(i): Conductors and equipment were not protected from overcurrent in accordance with their ability to safely conduct current: BOILER ROOM: The electrical panel (240AC / 600A) had 3/0 copper wire (approximately 200 Amp capacity) coming of the 600A bus bars to a secondary box, exposing employees to electrical and fire hazards.
Recent events (1)
- — Z (S) $0
More inspections at Bureau of Indian Affairs - T'Iis Nazbas Community School
View Bureau of Indian Affairs - T'Iis Nazbas Community School's full OSHA safety record →
More inspections in this industry (NAICS 611110)
More inspections in AZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346847064.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.