Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NATIONAL PARK SERVICE

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of NATIONAL PARK SERVICE in BUILDING 0-1517, DENALI NATIONAL PARK, AK 99755 (NAICS 321113). OSHA activity number 346849920.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service — free Get an email when a new federal OSHA severe-injury report for National Park Service is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 0-1517
City
DENALI NATIONAL PARK
State
AK
ZIP
99755
Mailing
P.O. BOX 9, DENALI NATIONAL PARK, AK 99755
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321113
Employees
5
Ownership type
D

5 citations on file for this inspection.

1910.106 D05 VI A

Serious Gravity 10 1 instance 5 exposed
Issued
Jan 12, 2024
Abate by
Apr 17, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(5)(vi)(a):  When the storage building was located 50 feet (15.2 m) or less from a building or line of adjoining property that could  be built upon, the exposing wall was not a blank wall having a fire-resistance rating of at least 2 hours:  a)  On or about July 18, 2023, the outside flammable storage building contained portable gas containers in a wooden structure that did not have a wall with  fire resistance rating of at least 2 hours and was located less than 5 feet to the adjoining trail maintenance shop, exposing employees to fire hazards.
Recent events (1)
  • — Z (S) $0

1910.106 E03 V A

Serious Gravity 5 1 instance 5 exposed
Issued
Jan 12, 2024
Abate by
Apr 17, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(3)(v)(a):  Areas as defined in paragraph (e)(3)(i) of this section using Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), were not ventilated at a rate of not less than 1 cubic foot per minute per square foot of solid floor area. This shall be accomplished by natural or mechanical ventilation with discharge or exhaust to a safe location outside of the building. Provision shall be made for introduction of makeup air in such a manner as not to short circuit the ventilation. Ventilation was not arranged to include all floor areas or pits where flammable vapors may collect:   a)  On or about July 18, 2023, the outside flammable storage building contained portable gas containers in a wooden structure that did not have ventilation and was located less than 5 feet to the adjoining trail maintenance shop, exposing employees to fire hazards.
Recent events (1)
  • — Z (S) $0

1910.110 B06 I

Serious Gravity 5 1 instance 5 exposed
Issued
Jan 12, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.110(b)(6)(i):  Containers and first stage regulating equipment of liquid petroleum gases were not located outside of the building:  a)  Flammable Storage Building:  On or about July 18, 2023, the outside flammable storage building contained a 20 pound LP portable gas container along with liquid gasoline in a wooden structure, exposing employees to explosion and fire hazards.  b) Flammable cabinets:  On or about July 18, 2023, six small portable propane containers were found inside the flammable cabinets along with other flammable materials, exposing employees to fire hazards.
Recent events (1)
  • — Z (S) $0

1910.1200 H02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Jan 12, 2024
Abate by
May 24, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(h)(2)(i):  The employer did not provide information to the employees on the requirements of the Hazard Communication Standard 29 CFR 1910.1200:  a) Flammable Cabinet:  On or about July 18, 2023, containers of camp fuel and charcoal lighter were stored along with other flammable materials exposing employees to explosion and fire hazards.  Specifically, paragraph (g)(2)(vii), Section 7, Handling and storage was not reviewed or followed.
Recent events (1)
  • — Z (S) $0

1910.1200 F06 I

Serious Gravity 1 1 instance 5 exposed
Issued
Jan 12, 2024
Abate by
Apr 17, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(f)(6)(i):  Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the information required by 29 CFR 1910.1200(f)(1)(i) through 29 CFR 1910.1200(f)(1)(v):   a) trail maintenance log cut area:  On or about July 18, 2023, clear plastic containers with amber liquid was not marked or labeled as required, exposing employees to unknown chemical hazards.  b) flammable cabinet:  On or about July 18, 2023, clear plastic container with the marking 5W20 Engine Oil was not marked or labeled as required, exposing employees to chemical hazards.
Recent events (1)
  • — Z (S) $0

View National Park Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346849920.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.