JACKSONVILLE, FL —
OSHA Inspection: SHORELINE PLASTICS, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of SHORELINE PLASTICS, LLC in 7167 OLD KINGS N ROAD, JACKSONVILLE, FL 32219 (NAICS 326199). OSHA activity number 346861693.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SHORELINE PLASTICS, LLC
- Site address
- 7167 OLD KINGS N ROAD
- City
- JACKSONVILLE
- State
- FL
- ZIP
- 32219
- Mailing
- 7167 OLD KINGS N ROAD, JACKSONVILLE, FL 32219
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 57
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.147 C04 I
- Issued
- Oct 17, 2023
- Abate by
- Dec 5, 2023
- Penalty
- Initial $7,813 · Current $5,333 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a. At 7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023 the employer exposed employees to potential hazardous energies in that employees were required to work on equipment to include but not limited to the American Maplan's Vacuum Chamber which had multiple energy sources such as electric and thermal, without those employees having been provided with written machine specific lock out procedure(s) to utilize to ensure that those energy sources were controlled while the employees were performing maintenance or servicing on the machine.
Recent events (2)
- — I (S) $5333.34
- — Z (S) $7813
1910.147 C04 II
- Issued
- Oct 17, 2023
- Abate by
- Dec 5, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4)(ii): Procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, 29 CFR 1910.147(c)(4)(ii)(A), (c)(4)(ii)(B), (c)(4)(ii)(C) and (c)(4)(ii)(D): a. At 7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the employer exposed employees to electric shock and thermal burns hazards, in that the employer's Lockout/Tagout Procedures for production line #4 did not specifically outline the rules and steps for the control the hazardous energy for equipment with more than one source of hazardous energy, such as the Krauss Maffei's Extruder, which had also thermal energy. b. At 7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the employer exposed employees to electric shock and thermal burns hazards, in that the employer's Lockout/Tagout Procedures for production line #4 did not specifically outline the scope, purpose, rules and steps for the control of hazardous energy for equipment with more than one source of hazardous energy, such as the American Maplan's Vacuum Chamber, among other machinery.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C06 I
- Issued
- Oct 17, 2023
- Abate by
- Dec 5, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct an annual or more frequent inspection of the energy control procedure to ensure that the procedure and requirements of this standard were followed: a. At 7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the employer exposed employees to electric shock and thermal burns hazards, in that periodic inspections of the energy control procedures were not being conducted as required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Oct 17, 2023
- Abate by
- Nov 13, 2023
- Penalty
- Initial $7,813 · Current $5,333 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a. At the Southwest wall of the Production building (Bld #2) located at7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the employer exposed employees to electrical hazards in that the Square D Company 480-V electrical switchboard had circuit breakers in the ON position that were not marked to indicate their purpose.
Recent events (2)
- — I (O) $5333.33
- — Z (S) $7813
1910.305 B01 II
- Issued
- Oct 17, 2023
- Penalty
- Initial $7,813 · Current $5,333 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a. At the Southwest wall of the Production building (Bld #2) located at7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the employer exposed employees to electrical hazards in that the Square D Company 480-V electrical switchboard had a circuit breakers in the ON position that was missing a cover.
Recent events (2)
- — I (S) $5333.33
- — Z (S) $7813
1910.178 L01 I
- Issued
- Oct 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(1)(i):The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l): a. At 7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the employer exposed employees to struck-by hazards, in that, forklift operators had not been trained and evaluated on the performance to ensure that they had the necessary knowledge and skills for the safe operation of the vehicle.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 B07 IV
- Issued
- Oct 17, 2023
- Abate by
- Nov 13, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: a. At 7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the employer exposed employees to electrical shock hazards and arc-flash hazards, in that the main power disconnect switch of the electric panel that fed the blue hammer mill was broken and the door of the panel could not effectively closed. b. At 7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the employer exposed employees to electrical shock hazards, in that the main power disconnect switch for the electric panel of the vacuum tank in production line #4 was broken.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 II
- Issued
- Oct 17, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a. At the Southwest wall of the Production building located at7167 Old Kings N Road, Jacksonville, FL, on or about July 24, 2023: the working space required in front of the Square D Company 480-V electrical switchboard was being used for storage, obstructing the access for equipment emergency shutdown, examination, adjustment, servicing or maintenance.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Shoreline Plastics, LLC
View Shoreline Plastics, LLC's full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346861693.