Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ACME BRICK CO

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ACME BRICK CO in 4103 DAWSON ROAD, TULSA, OK 74115 (NAICS 327120). OSHA activity number 346921737.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Acme Brick CO — free Get an email when a new federal OSHA severe-injury report for Acme Brick CO is published. One employer, no account, unsubscribe in one click.
Establishment
ACME BRICK CO
Site address
4103 DAWSON ROAD
City
TULSA
State
OK
ZIP
74115
Mailing
4103 DAWSON ROAD, TULSA, OK 74115
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327120
Employees
57
Ownership type
A

8 citations on file for this inspection.

1910.22 A01

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 6, 2024
Penalty
Initial $5,876 · Current $3,526 Reduced
29 CFR  1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition.  On or about August 15, 2023 and at times prior thereto, in the basement of the facility, large piles of sand and rocks cover the walking working surface and ramp/stairs leading to the basement.  This exposes employees to trip and fall hazards.
Recent events (2)
  • — I (S) $3525.6
  • — Z (S) $5876

1910.178 Q01

Serious Gravity 5 2 instances 2 exposed
Issued
Feb 6, 2024
Penalty
Initial $7,835 · Current $4,701 Reduced
29 CFR 1910.178(q)(1): Power-operated industrial truck not in safe operating condition were not taken out of service, and/or repairs were not made by authorized personnel:   a.)	On or about August 17, 2023 and at times prior thereto, Caterpillar forklift #3451 was observed in service with a broken front and rear windshield.  This exposed the employees to struck-by hazards.     b.)	On or about August 17, 2023 and at times prior thereto, Caterpillar forklift #3452 was observed in service with a broken rear windshield.  This exposed the employees to struck-by hazards.
Recent events (2)
  • — I (S) $4701
  • — Z (S) $7835

1910.212 A05

Serious Gravity 5 2 instances 2 exposed
Issued
Feb 6, 2024
Penalty
Initial $7,835 · Current $4,701 Reduced
29 CFR 1910.212(a)(5): Fan blade guard(s) were not provided where the periphery of the blades was less than seven feet from the floor or working level:                                                                                                              a.)	On or about August 17, 2023, by the middle transfer table, employees were in use of a large floor fan with openings greater than a half inch on the fan blade cover.  This exposed the employees to a caught-in hazard.         b.)	On or about August 17, 2023, in the basement, employees were in use of a large floor fan with openings greater than a half inch on the fan blade cover.  This exposed the employees to a caught-in hazard.
Recent events (2)
  • — I (S) $4701
  • — Z (S) $7835

1910.305 A01 I

Serious Gravity 5 2 instances 1 exposed
Issued
Feb 6, 2024
Penalty
Initial $7,835 · Current $4,701 Reduced
29 CFR 1910.305(a)(1)(i): Metal raceways, cable trays, cable armor, cable sheath, and other metal enclosures for conductors were not metallically joined together into a continuous electric conductor:    a.)	On or about August 17, 2023, the raceway on the bottom of the middle transfer table was pulled away from its enclosure.  This exposed the employees to an electrical hazard.         b.)	On or about August 17, 2023,  the raceway on the bottom of the middle transfer table control box was pulled away from its enclosure. This exposed the employees to an electrical hazard.
Recent events (2)
  • — I (S) $4701
  • — Z (S) $7835

1910.305 B02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 6, 2024
Penalty
Initial $7,835 · Current $4,701 Reduced
29 CFR  1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings in completed installations were not provided with covers approved for the purpose:   On or about August 17, 2023, an electrical box containing energized electrical wiring was observed with a missing cover.  This exposed an employee to an electrical hazard.
Recent events (2)
  • — I (S) $4701
  • — Z (S) $7835

1910.305 G01 IV A

Serious Gravity 1 3 instances 3 exposed
Issued
Feb 6, 2024
Penalty
Initial $5,876 · Current $3,526 Reduced
29 CFR 1910.305(g)(1)(iv)(A):  Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:                                                                                                                            a.)	On or about August 17, 2023 and at times prior thereto, by the middle transfer table, an extension cord (flexible cord) was being used as a substitute for fixed wiring and was wrapped around other cords and parts of the structure.  This exposed employees to electrical hazards.         b.)	On or about August 17, 2023, in the basement of the facility, an extension cord (flexible cord) was secured to parts of the structure. This exposed employees to electrical hazards.    c.)	On or about August 17, 2023,  in the Pug Mill, an extension cord (flexible cord) was secured to parts of the structure.  This exposed employees to electrical hazards.
Recent events (2)
  • — I (S) $3525.6
  • — Z (S) $5876

1910.334 A03 I

Serious Gravity 5 2 instances 1 exposed
Issued
Feb 6, 2024
Penalty
Initial $7,835 · Current $4,701 Reduced
29 CFR 1910.334 (a)(3)(i): A flexible cord used with grounding type equipment did not contain an equipment grounding conductor:                                                                                                                           Flexible cords are observed in use and missing grounds prongs, exposing employees to electrical hazards.    a.) On or about August 17, 2023, a metal cased floor fan was missing the ground prong on the fan cord.  This exposed the employees to an electrical hazard.    b.) On or about August 17, 2023, a metal cased heat lamp was missing the ground prong on the lamp cord. This exposed the employees to an electrical hazard.
Recent events (2)
  • — I (S) $4701
  • — Z (S) $7835

1910.157 C01

Other-than-serious 1 instance 1 exposed
Issued
Feb 6, 2024
Abate by
Mar 4, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:      On or about August 15, 2023, a fire extinguisher mounted on a pole was missing marking illustrating the location of the fire extinguisher.  This exposed employees to a fire hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Acme Brick CO's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346921737.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.