OSHA Inspection: DEFLEX INNOVATIONS INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of DEFLEX INNOVATIONS INC. in 22 JERICHO ROAD, BERLIN, NH 03570 (NAICS 336211). OSHA activity number 347007056.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Deflex Innovations INC. — free Get an email when a new federal OSHA severe-injury report for Deflex Innovations INC. is published. One employer, no account, unsubscribe in one click.
Site address
22 JERICHO ROAD
City
BERLIN
State
NH
ZIP
03570
Mailing
22 JERICHO ROAD, BERLIN, NH 03570
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336211
Employees
7
Ownership type
A

8 citations on file for this inspection.

1910.106 D04 I

Serious Gravity 5 1 instance 7 exposed
Issued
Dec 6, 2023
Abate by
Jan 25, 2024
Penalty
Initial $3,349 · Current $1,675 Reduced
29 CFR 1910.106(d)(4)(i): Openings to other rooms or buildings were not provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, or the floor in the storage area were not at least 4 inches below the surrounding floor.  A permissible alternate to the sill or ramp consisting of an open-grated trench inside of the room which drains to a safe location had not been established.  Openings were not provided with approved self-closing fire doors.   Location: Flammable storage room  On or about October 3, 2023, employees were exposed to fire hazards when the employer stored drums of acetone and fiberglass resin in a closed flammables storage room that was not designed for flammable storage.
Recent events (2)
  • — I (S) $1674.5
  • — Z (S) $3349

1910.106 D04 IV

Serious Gravity 5 1 instance 7 exposed
Issued
Dec 6, 2023
Abate by
Apr 30, 2024
Penalty
Initial $3,349 · Current $1,675 Reduced
29 CFR 1910.106(d)(4)(iv): Each inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system designed to provide for a complete change of air within the room at least six times per hour.  Location: Flammable storage room  On or about October 3, 2023, the flammable material storage room did not have a ventilation system to supply at least six air changes per hour.
Recent events (2)
  • — I (S) $1674.5
  • — Z (S) $3349

1910.134 C01

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 6, 2023
Abate by
Jan 10, 2024
Penalty
Initial $2,679 · Current $1,340 Reduced

Hazardous substances 9135

29 CFR 1910.134(c)(1):  A written respiratory protection program that included the provisions in 29 CFR 1910.134(c)(1)(i) - (ix) with worksite specific procedures was not established and implemented for required respirator use:  Location: Cutting and Sanding Area  On or about October 3, 2023, the employer did not establish and implement a written respiratory protection program for employees required to wear a respirator.
Recent events (2)
  • — I (S) $1339.5
  • — Z (S) $2679

1910.134 E01

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 6, 2023
Abate by
Jan 10, 2024
Penalty
Initial $0 · Current $0

Hazardous substances 9135

29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace:  Location: Cutting and Sanding Area  On or about October 3, 2023, employees required to wear respirators were not medically evaluated by the employer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 F02

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 6, 2023
Abate by
Jan 10, 2024
Penalty
Initial $0 · Current $0

Hazardous substances 9135

29 CFR 1910.134(f)(2): Employee(s) using tight-fitting facepiece respirators were not fit tested prior to initial use of the respirator:  Location: Cutting and Sanding Area  On or about October 3, 2023, employees required to wear respirators were not fit tested prior to wearing an N95 respirator.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 G01 I A

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 6, 2023
Abate by
Jan 10, 2024
Penalty
Initial $0 · Current $0

Hazardous substances 9135

29 CFR 1910.134(g)(1)(i)(A): Respirators with tight-fitting facepieces were worn by employees who had facial hair that came between the sealing surface of the facepiece and the face or that interfered with valve function:   Location: Cutting and Sanding Area  On or about October 3, 2023, an employee wore an N95 respirator while having facial hair that impeded the respirators' ability to make a seal with the face.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 K

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 6, 2023
Abate by
Jan 10, 2024
Penalty
Initial $0 · Current $0

Hazardous substances 9135

29 CFR 1910.134(k): The employer did not provide comprehensive, understandable training which did not occur annually and/or more often if necessary:  Location: Cutting and Sanding Area  On or about October 3, 2023, employees required to wear respirators were not trained prior to wearing an N95 respirator.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.307 C02 I

Serious Gravity 5 1 instance 7 exposed
Issued
Dec 6, 2023
Abate by
Apr 30, 2024
Penalty
Initial $3,349 · Current $1,675 Reduced
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present:  Location: Flammable Storage Room  On or about October 3, 2023, lighting and electrical equipment in the flammable storage room (a class 1, division 2 area) were not rated to prevent the ignition of flammable liquids or vapors from acetone and fiberglass resin.
Recent events (2)
  • — I (S) $1674.5
  • — Z (S) $3349

View Deflex Innovations INC.'s full OSHA safety record →