Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NATIONAL WEATHER SERVICE - SAN JUAN FORECAST OFFICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL WEATHER SERVICE - SAN JUAN FORECAST OFFICE in 4000 STATE ROAD PR 190, CAROLINA, PR 00979 (NAICS 541990). OSHA activity number 347014284.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Weather Service - SAN Juan Forecast Office — free Get an email when a new federal OSHA severe-injury report for National Weather Service - SAN Juan Forecast Office is published. One employer, no account, unsubscribe in one click.
Site address
4000 STATE ROAD PR 190
City
CAROLINA
State
PR
ZIP
00979
Mailing
4000 STATE ROAD PR 190, CAROLINA, PR 00979
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541990
Employees
23
Ownership type
D

5 citations on file for this inspection.

1910.37 A04

Serious Gravity 1 1 instance 3 exposed
Issued
Nov 2, 2023
Abate by
Nov 17, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.37(a)(4):Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:  a) On or about October 5th, 2023, at the National Weather Service, Generator Room, an emergency light, Brand SURE LITES, was inoperative and with electrical cables exposed.  This condition can expose employees to fire hazards.  NOTE: Certification and documentation of abatement must be submitted for this citation item as required by CFR 1903.19(c) and (d), respectively.
Recent events (1)
  • — Z (S) $0

1910.151 C

Serious Gravity 5 2 instances 3 exposed
Issued
Nov 2, 2023
Abate by
Nov 17, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.151(c):Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  a) On or about October 5th, 2023, at the National Weather Service, Electrical Room, there was one portable eyewash bottle, Brand, Bradley with the solution expired since August, 2006, exposing employees to eye injuries.  b) On or about October 5th, 2023, at the National Weather Service, Generator Room, there was one portable eyewash bottle, Brand, unknown with the solution expired since March 2010, exposing employees to eye injuries.   NOTE: Certification and documentation of abatement must be submitted for these citations items as required by CFR 1903.19(c) and (d), respectively.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Serious Gravity 5 1 instance 3 exposed
Issued
Nov 2, 2023
Abate by
Nov 17, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.157(c)(1):Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  a) On or about October 5th, 2023, at the National Weather Service, Outdoor Storage Room, a Fire Extinguisher CO2, Brand General, Serial No. unknown and Fire Extinguisher Halon, Brand Sentry, Serial No, unknown, 5 pounds, were placed on the floor, exposing employees to fire hazards and contusions in case of accidental knocking.  NOTE: Certification and documentation of abatement must be submitted for this citation item as required by CFR 1903.19(c) and (d), respectively.
Recent events (1)
  • — Z (S) $0

1910.157 E02

Serious Gravity 5 1 instance 3 exposed
Issued
Nov 2, 2023
Abate by
Nov 17, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(2):Portable fire extinguishers were not visually inspected at least monthly:  a) On or about October 5th, 2023, at the National Weather Service, Inflation Room, a fire extinguisher ABC Dry Chemical, Model Amerex A411, Serial No. RO150711, a CO2, Fire Extinguisher, 20 pounds Serial No. unknown, and a CO2 fire extinguisher, Brand, General, Serial No. 362952, were not inspected monthly according to the inspection records tag, exposing employees to fire hazards.  NO PHOTOS ALLOWED IN THIS ROOM.   NOTE: Certification and documentation of abatement must be submitted for this citation item as required by CFR 1903.19(c) and (d), respectively.
Recent events (1)
  • — Z (S) $0

1910.157 E03

Serious Gravity 5 7 instances 23 exposed
Issued
Nov 2, 2023
Abate by
Nov 17, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(3):Portable fire extinguishers were not subjected to an annual maintenance check:  a) On or about October 5th, 2023, at the National Weather Service, Communications Room, a fire extinguisher Halotron, Serial No. C-98763438, 11 pounds, was not subjected to the annual maintenance check exposing employees to fire hazards.  Overdue for the inspection since August 2023.    b) On or about October 5th, 2023, at the National Weather Service, Hallway, a fire extinguisher ABC Dry Chemical, Serial No. C-99289390, 10 pounds, was not subjected to the annual maintenance check exposing employees to fire hazards.  Overdue for the inspection since August 2023.  c) On or about October 5th, 2023, at the National Weather Service, Electronics Technician Room, a fire extinguisher ABC Dry Chemical, Serial No. C-99288008, 10 pounds, was not subjected to the annual maintenance check exposing employees to fire hazards.  Overdue for the inspection since August 2023.  d) On or about October 5th, 2023, at the National Weather Service, Generator Room, a fire extinguisher CO2, Serial No. 363007, was not subjected to the annual maintenance check exposing employees to fire hazards.  Overdue for the inspection since August 2023.   e) On or about October 5th, 2023, at the National Weather Service, Outdoor Storage Room, a fire extinguisher ABC Dry Chemical, Serial No. LV 00010830, 10 pounds, was not subjected to the annual maintenance check exposing employees to fire hazards.  Overdue for the inspection since August 2023.   f) On or about October 5th, 2023, at the National Weather Service, Heating, Ventilation and Air Conditioning (HVAC) Room, a fire extinguisher CO2, Serial No. J-68916, was not subjected to the annual maintenance check exposing employees to fire hazards.  Overdue for the inspection since August 2023.  g) On or about October 5th, 2023, at the National Weather Service, Inflation Room, a fire extinguisher ABC Dry Chemical, Model Amerex A411, Serial No. RO150711, a CO2, Fire Extinguisher, 20 pounds Serial No. unknown, and a CO2 fire extinguisher, Brand, General, Serial No. 362952, were not subjected to the annual maintenance check exposing employees to fire hazards.  Overdue for the inspection since August 2023. NO PHOTOS ALLOWED IN THIS ROOM.   NOTE: Certification and documentation of abatement must be submitted for all instances of this citation item as required by CFR 1903.19(c) and (d), respectively.
Recent events (1)
  • — Z (S) $0

View National Weather Service - SAN Juan Forecast Office's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347014284.