SARCOXIE, MO —
OSHA Inspection: BROOKS GREASE
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BROOKS GREASE in 1083 LAWRENCE 2140, SARCOXIE, MO 64862 (NAICS 562998). OSHA activity number 347026643.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BROOKS GREASE
- Site address
- 1083 LAWRENCE 2140
- City
- SARCOXIE
- State
- MO
- ZIP
- 64862
- Mailing
- 3104 N ERIE AVENUE, TULSA, OK 74155
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 562998
- Employees
- 3
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.146 C01
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $14,518 · Current $8,710 Reduced
General-duty citation text
29 CFR 1910.146(c)(1):The employer did not evaluate the workplace to determine if any spaces were permit-required confined spaces. At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to potentially hazardous atmospheres and engulfment hazards in that the employer did not determine if spaces employees worked in were classified as permit-required confined spaces.
Recent events (2)
- — I (S) $8710
- — Z (S) $14518
1910.146 C04
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.146(c)(4):If the employer decides that its employees will enter permit spaces, the employer shall develop and implement a written permit space program that complies with this section. The written program shall be available for inspection by employees and their authorized representatives. At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to potentially hazardous atmospheres and engulfment hazards in that the employer did not implement a written permit- required confined space program before employees worked in spaces that could be classified as permit- required confined spaces.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $8,296 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2):Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to electric shock hazards in the following instances. a) Permanently affixing relocatable power strips to to metal conduit. b) Interconnecting relocatable power strips with extension cords.
Recent events (2)
- — I (S) $0
- — Z (S) $8296
1910.303 F02
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $6,222 · Current $3,733 Reduced
General-duty citation text
29 CFR 1910.303(f)(2):Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to potential struck by hazards in that the overcurrent device that controlled the North Star air compressor was not properly labeled.
Recent events (2)
- — I (S) $3733
- — Z (S) $6222
1910.303 G02 I
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $10,372 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i):Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to electrical hazards a)The electrical panel in the shop was missing the dead front and filler plates, exposing employees to live electrical parts. b)The electrical panel in the office was missing the dead front, exposing employees to live electrical parts.
Recent events (2)
- — I (S) $0
- — Z (S) $10372
1910.304 F01 VI
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $8,296 · Current $4,977 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(vi):Circuit breakers did not clearly indicate whether they are in the open (off) or closed (on) position. At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to electrical hazards in that the circuit breakers in the shop did not clearly indicate whether they were in the open (off) or closed (on) position.
Recent events (2)
- — I (S) $4977
- — Z (S) $8296
1910.305 G01 IV A
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $6,222 · Current $6,222
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A):Flexible cords and cables were used as a substitute for the fixed wiring of a structure: At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to electrical shock and fire hazards in that the employer used extension cords in lieu of fixed wiring.
Recent events (2)
- — I (O) $6222
- — Z (S) $6222
1910.305 G01 IV B
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B):Flexible cords and cables may not be used where run through holes in walls, ceilings or floors: At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to electrical shock and fire hazards in that the employer ran flexible wire for lighting through the shop walls.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Mar 22, 2024
- Abate by
- Apr 17, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D):Flexible cords and cables were used where attached to building surfaces: At the workplace located at 1083 Lawrence 2140, Sarcoxie, MO 64862: Employees were exposed to electrical shock and fire hazards in that the employer attached flexible cords to the building surface.
Recent events (2)
- — I (O) $0
- — Z (S) $0
More inspections at Brooks Grease
View Brooks Grease's full OSHA safety record →
More inspections in this industry (NAICS 562998)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347026643.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.