LINCOLN, CA —
OSHA Inspection: THUNDER VALLEY CASINO RESORT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of THUNDER VALLEY CASINO RESORT in 1200 ATHENS AVENUE, LINCOLN, CA 95648 (NAICS 721120). OSHA activity number 347048407.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THUNDER VALLEY CASINO RESORT
- Site address
- 1200 ATHENS AVENUE
- City
- LINCOLN
- State
- CA
- ZIP
- 95648
- Mailing
- 1200 ATHENS AVENUE, LINCOLN, CA 95648
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721120
- Employees
- 1100
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.22 A02
- Issued
- Jan 18, 2024
- Abate by
- Jan 30, 2024
- Penalty
- Initial $11,754 · Current $8,228 Reduced
General-duty citation text
29 CFR 1910.22(a)(2): The floor of each workroom was not maintained in a dry condition. When wet processes are used, mats were not provided. In the dishwashing area of the employee kitchen, the floor was observed to be wet from a leaking dishwashing machine. Employees are exposed to slip and fall hazards.
Recent events (2)
- — I (S) $8227.8
- — Z (S) $11754
1910.22 A03
- Issued
- Jan 18, 2024
- Abate by
- Jan 30, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(3):(3) Walking-working surfaces were not maintained free of hazards such as sharp or protruding objects. In the kitchen, the long drain near the Hobart mixer was raised, protruding above the floor. Employees are exposed to tripping hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 E03
- Issued
- Jan 18, 2024
- Abate by
- Jan 30, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3):The employer did not assure that portable fire extinguishers are subjected to an annual maintenance check. In "The Venue": 1.In the main bar storage lobby, a fire extinguisher was found without an annual maintenance check record. 2. In the elevator room, a fire extinguisher was found without an annual maintenance check record. In both instances, employees were exposed to fire and smoke hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 B02
- Issued
- Jan 18, 2024
- Abate by
- Jan 30, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not used in accordance with any instructions included in the listing or labeling. In "The Venue": 1. In the Audio/Visual room at the south end of the stage, a microwave was found plugged into a power strip. 2. In the Admin room, a microwave was found plugged into a power strip. In both cases, employees are exposed to fire smoke, and electrical shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01
- Issued
- Jan 18, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. In an electrical room off the main employee hallway at the east end of the casino, electrical panels 1LS2A and 1LS2B were blocked by a cart. Employees were exposed to fire and smoke hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 III
- Issued
- Jan 18, 2024
- Penalty
- Initial $1,100 · Current $770 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iii): Flexible cords were not energized from an approved receptacle outlet. 1. In the equipment storage room off the north end of the stage, an extension cord was observed plugged into a power strip. 2. In the TVCR Staff & Crew room, an extension cord was observed plugged into a power strip powering a fan. 3. In the soldering room, 2 power strips were found daisy-chained into other power strips. In all instances, employees are exposed to fire hazards.
Recent events (2)
- — I (O) $770
- — Z (O) $1100
1910.305 G01 IV A
- Issued
- Jan 18, 2024
- Abate by
- Jan 30, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. In "The Venue", off the north end of the stage in the equipment storage room, a black extension cord was observed zip-tied up from a power strip, along HVAC ducting, and down to a desk. Employees are exposed to fire and smoke hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 IV D
- Issued
- Jan 18, 2024
- Abate by
- Jan 30, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): A flexible cord or cable was attached to building surfaces. 1. In the equipment storage room off the north end of the stage, a power strip was found attached to storage racking. 2. In the laundry room, a power strip was found attached to the wall. In both instances, employees were exposed to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.334 A02 I
- Issued
- Jan 18, 2024
- Abate by
- Jan 30, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(i):Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket). 1. In the Subway restaurant, the meat slicer had a damaged outer jacket, exposing the internal wires. 2. In the fabrication shop, an extension cord had a damaged outer jacket, exposing the internal wires. In both instances, employees were exposed to electrical shock hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Thunder Valley Casino Resort
View Thunder Valley Casino Resort's full OSHA safety record →
More inspections in this industry (NAICS 721120)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347048407.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.