FORT WAINWRIGHT, AK —
OSHA Inspection: U.S. ARMY
Follow-up inspection · Safety discipline
At a glance
On , OSHA opened a follow-up safety inspection of U.S. ARMY in FIRE STATIONS 1, 2, & 3, FORT WAINWRIGHT, AK 99703 (NAICS 922160). OSHA activity number 347111577.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. ARMY
- Site address
- FIRE STATIONS 1, 2, & 3
- City
- FORT WAINWRIGHT
- State
- AK
- ZIP
- 99703
- Mailing
- 1046 MARKS ROAD #6000, FORT WAINWRIGHT, AK 99703
What kind of inspection was it?
- Inspection type
- Follow-up (F)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 922160
- Employees
- 66
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.22 D02
- Issued
- Mar 20, 2024
- Abate by
- Apr 1, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(d)(2): The employer did not ensure that hazardous conditions on walking-working surfaces are corrected or repaired before an employee uses the walking-working surface. a) Station #1 (ARFF)/Flight line Stalls: On or about November 15, 2023, spalling concrete in vehicle stalls was not repaired, exposing employees to trip and fall hazards.
Recent events (2)
- — P (S) $0
- — Z (S) $0
1910.304 G06 IV B
- Issued
- Mar 20, 2024
- Abate by
- Apr 1, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(6)(iv)(B): The receptacle was located in a wet or damp environment and was not grounded: a) Fire Station #2, Bathroom: On or about November 15, 2023, an electrical outlet was without a Ground Fault Circuit Interrupter in near proximity of a bathroom sink, exposing employees to electrical hazards.
Recent events (2)
- — P (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Mar 20, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Station #1 Flight Line, Day Room: On or about November 15, 2023, two surge protectors were connected together creating a daisy chain, exposing employees to electrical shock and fire hazards.
Recent events (1)
- — Z (O) $0
1910.303 G01 I B
- Issued
- Mar 20, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : a) Fire Station #1, Next to work table: On or about November 15, 2023, a Shop Vac and Water Cooler were obstructing the electrical panel, exposing employees to electrical hazards. b) Fire Station #2, Ambulance Bay: On or about November 15, 2023, a patient gurney was obstructing the electrical panel, exposing employees to electrical hazards.
Recent events (1)
- — Z (O) $0
More inspections at U.S. Army
View U.S. Army's full OSHA safety record →
More inspections in this industry (NAICS 922160)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347111577.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.