EL PASO, TX —
OSHA Inspection: BROKERS LOGISTICS, LTD.
Programmed Related inspection · Safety discipline
At a glance
On , OSHA opened a programmed Related safety inspection of BROKERS LOGISTICS, LTD. in 1000 HAWKINS BLVD, EL PASO, TX 79915 (NAICS 493110). OSHA activity number 347133969.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BROKERS LOGISTICS, LTD.
- Site address
- 1000 HAWKINS BLVD
- City
- EL PASO
- State
- TX
- ZIP
- 79915
- Mailing
- 6830 INDUSTRIAL, EL PASO, TX 79915
What kind of inspection was it?
- Inspection type
- Programmed Related (J)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 80
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.157 E03
- Issued
- Jan 11, 2024
- Penalty
- Initial $5,424 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check. On or about November 30, 2023, the employer did not ensure the fire extinguishers on the forklifts were inspected on annual bias on three different instances: a) Forklift 114 (Serial # 72272) b) Forklift 16 (Serial # 60418) c) Forklift 150 (Serial # 72282)
Recent events (2)
- — I (S) $2500
- — Z (S) $5424
1910.303 B07 I
- Issued
- Jan 11, 2024
- Penalty
- Initial $9,041 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: On or about November 30, 2023, in warehouse C, employees were exposed to electrical shock hazards due to unused openings on electrical boxes exposing live conductors.
Recent events (2)
- — I (S) $5000
- — Z (S) $9041
1910.305 B02 I
- Issued
- Jan 11, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about November 30, 2023, in warehouse C near the breaker panel the employer did not ensure each outlet had a suitable faceplate. This exposed employees to electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 B03 II A
- Issued
- Jan 11, 2024
- Penalty
- Initial $5,424 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that were not part of the permanent wiring of the building or structure and that were in use by personnel did not have ground-fault circuit-interrupter protection for personnel. On or about November 30, 2023, an electrical receptacle near a water source in the employee's breakroom did not have a ground-fault circuit interrupter, this condition exposed employees to electrical shock hazards.
Recent events (2)
- — I (S) $2500
- — Z (S) $5424
1910.305 A02 X
- Issued
- Jan 11, 2024
- Penalty
- Initial $12,656 · Current $6,000 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables shall be protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points. On or about November 30,2023, in the RG Ray department, employees working in warehouse B were exposed to electrical shock hazards when the outer/inner insulation of the extension cord was severely damaged exposing the live copper conductors.
Recent events (2)
- — I (S) $6000
- — Z (S) $12656
1910.303 G01 I B
- Issued
- Jan 11, 2024
- Abate by
- Feb 1, 2024
- Penalty
- Initial $1,015 · Current $500 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment that is likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 30 inches, whichever was greater. On or about November 30, 2023, two electrical panels in the warehouse B did not have 30 inches of clearance. This exposed employees to an electrical shock hazard. a) Northeast location (near RG Ray workstation). b) Southeast of the building.
Recent events (2)
- — I (O) $500
- — Z (O) $1015
1910.305 G02 III
- Issued
- Jan 11, 2024
- Penalty
- Initial $1,015 · Current $500 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws. On or about November 30, 2023, employees in warehouse C working near dock 41 were exposed to electrical shock hazards when the employer did not ensure the strain relief provided prevented pulling of the electrical wires.
Recent events (2)
- — I (O) $500
- — Z (O) $1015
More inspections at Brokers Logistics, LTD.
View Brokers Logistics, LTD.'s full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347133969.