Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ERIE STRAYER COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ERIE STRAYER COMPANY in 1851 RUDOLPH AVENUE, ERIE, PA 16502 (NAICS 333120). OSHA activity number 347177032.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Erie Strayer Company — free Get an email when a new federal OSHA severe-injury report for Erie Strayer Company is published. One employer, no account, unsubscribe in one click.
Site address
1851 RUDOLPH AVENUE
City
ERIE
State
PA
ZIP
16502
Mailing
1851 RUDOLPH AVENUE, ERIE, PA 16502
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333120
Employees
91
Ownership type
A

2 citations on file for this inspection.

1910.333 A02

Serious Gravity 5 1 instance 1 exposed
Issued
May 29, 2024
Abate by
Jun 25, 2024
Penalty
Initial $6,453 · Current $4,517 Reduced
29 CFR  1910.333(a)(2): Where exposed live parts were not deenergized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved:    a.) Erie Strayer Company, Overhead door #5 area, on or about December 04, 2023, and times prior thereto:  Employee removed the cover to the energized 480V control box for overhead door #5 to access the control lever while performing maintenance work. Personal protective equipment including, but not limited to, electrically rated gloves, arc rated long sleeve or coverall, arc rated pants, arc rated balaclava, and arc rated suit hood or face shield were not utilized while operating the lever in the door #5 control box.
Recent events (2)
  • — I (S) $4517.1
  • — Z (S) $6453

1910.332 B01

Serious Gravity 5 1 instance 1 exposed
Issued
May 29, 2024
Abate by
Jun 25, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.332(b)(1):Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  a.) Erie Strayer Company, Overhead door #5 area, on or about December 04, 2023, and times prior thereto: Worksite specific training was not conducted for employees performing electrical work. Electrical safe work practices were not covered with the authorized employee.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Erie Strayer Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347177032.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.