On , OSHA opened a referral safety inspection of MTD PRODUCTS, INC. in 979 S. CONWELL AVE., WILLARD, OH 44890 (NAICS 333112). OSHA activity number 347177990.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch MTD Products, INC. — free Get an email when a new federal OSHA severe-injury report for MTD Products, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
MTD PRODUCTS, INC.
Site address
979 S. CONWELL AVE.
City
WILLARD
State
OH
ZIP
44890
Mailing
979 S. CONWELL AVE., WILLARD, OH 44890
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333112
Employees
1247
Ownership type
A

6 citations on file for this inspection.

1910.28 B01 I

Serious Gravity 5 1 instance 15 exposed
Issued
May 15, 2024
Abate by
Nov 7, 2024
Penalty
Initial $12,676 · Current $12,676
29 CFR  1910.28(b)(1)(i):  Except as provided elsewhere in this section 29 CFR 1910.28, the employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i):  a. MTD Products, Inc. dba Stanley Black & Decker - Willard, Ohio: On or about December 15, 2023, employees were exposed to fall hazards of approximately 12-feet and nine inches when accessing the top of the Line 2 Dry-Off Oven for tasks such as, but not limited to, preventive maintenance and troubleshooting.  In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (3)
  • — F (S) $12676
  • — C (S) $12676
  • — Z (S) $12676

1910.333 A

Serious Gravity 10 1 instance 15 exposed
Issued
May 15, 2024
Abate by
Nov 7, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized.  MTD Products, Inc. dba Stanley Black & Decker - Willard, Ohio: On or about December 15, 2023, the employer did not develop and implement electrical safety related work practices (ESRWP) which cover employees exposed to live electrical conductors.  Employees responsible for performing electrical tests and fuse replacement in a 480-volt 60-amp electrical distribution panel for the dry-off oven were exposed to electrical hazards in that ESRWP such as, but not limited to, alerting techniques, approach boundaries/body positioning, deenergization, and electrical protective equipment, were not employed to prevent electrical shock and/or arc flash/blast injuries.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (3)
  • — F (S) $16131
  • — C (S) $16131
  • — Z (S) $16131

1910.333 C02

Serious Gravity 10 1 instance 15 exposed
Issued
May 15, 2024
Abate by
Nov 7, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.  a. MTD Products, Inc. dba Stanley Black & Decker - Willard, Ohio:  The employer did not ensure that workers who accessed the 480-volt\60 amp oven control electrical distribution panel for troubleshooting tasks were qualified.  Employees were not trained on procedures for working safely on energized parts in that employees were not familiar with the proper personal protective equipment while voltage testing energized parts.  In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.333 A01

Serious Gravity 10 1 instance 15 exposed
Issued
May 15, 2024
Abate by
Nov 7, 2024
Penalty
Initial $16,131 · Current $0 Reduced
29 CFR  1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or was near to them:  a. MTD Products, Inc. dba Stanley Black & Decker - Willard, Ohio: On or about December 15, 2023, employee(s) were exposed to electrical hazards in that the electrical power for the oven control panel was not deenergized before employees accessed the panels to perform tasks such as, but not limited to, replacing fuses.  Employees were exposed electrical shock and arc flash/blast hazards while working on or near live parts in the 480V/60amp electrical control panel.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (3)
  • — F (S) $0
  • — C (S) $16131
  • — Z (S) $16131

1910.333 B02 I

Serious Gravity 10 1 instance 20 exposed
Issued
May 15, 2024
Abate by
Nov 7, 2024
Penalty
Initial $16,131 · Current $0 Reduced
29 CFR  1910.333(b)(2)(i):The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 and did not make it available for inspection by the Assistant Secretary of Labor and his or her authorized representatives:  a. MTD Products, Inc. - Willard, Ohio: On or about December 15, 2023, the employer did not develop written energy control procedures for the oven control panel.  Procedures to deenergize circuits, apply lockout devices, and verify the absence of power were not documented before employees accessed the panel to replace a fuse(s).   In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (3)
  • — F (S) $0
  • — C (S) $16131
  • — Z (S) $16131

1910.335 A01 I

Repeat Gravity 10 1 instance 15 exposed
Issued
May 15, 2024
Abate by
Nov 7, 2024
Penalty
Initial $161,323 · Current $161,323
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  a. MTD Products, Inc. - dba Stanley Black & Decker - Willard, Ohio:   On or about December 15, 2023, the employer did not ensure employees were protected from electrical hazards in that rubber insulated and leather gloves, hard hat, and arc rated face shield were not provided to employees who accessed the 480-volt/60-amp oven control electrical distribution panel. Employees were exposed to electrocution, shock, and arc flash/blast while troubleshooting/voltage testing within the panel.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence, or written records.
Recent events (3)
  • — F (R) $161323
  • — C (W) $161323
  • — Z (W) $161323