GLOUCESTER, MA —
OSHA Inspection: CAPE SEAFOODS INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CAPE SEAFOODS INC. in 3 STATE PIER, GLOUCESTER, MA 01930 (NAICS 424460). OSHA activity number 347184921.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CAPE SEAFOODS INC.
- Site address
- 3 STATE PIER
- City
- GLOUCESTER
- State
- MA
- ZIP
- 01930
- Mailing
- 3 STATE PIER, GLOUCESTER, MA 01930
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424460
- Employees
- 17
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.37 B04
- Issued
- Mar 28, 2024
- Abate by
- Apr 23, 2024
- Penalty
- Initial $3,918 · Current $2,743 Reduced
General-duty citation text
29 CFR 1910.37(b)(4) - Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: a) Location - 2nd Floor electrical room On or about 12/22/2023, a door leading from an electrical room to the adjacent path of egress was not marked with an "Exit" sign to indicate the direction of travel. b) Location - 2nd Floor hallway adjacent to storage room On or about 12/22/2023, a hallway leading to a stair case and means of egress was not marked with an "Exit" sign to indicate the direction of travel.
Recent events (2)
- — I (S) $2742.6
- — Z (S) $3918
1910.303 G01
- Issued
- Mar 28, 2024
- Abate by
- Apr 23, 2024
- Penalty
- Initial $3,918 · Current $2,743 Reduced
General-duty citation text
29 CFR 1910.303(g)(1) - Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Location - 2nd Floor Electrical Room On or about 12/22/2023, a set of live electrical panels were obstructed by stored materials including boxes of material, a traffic cone and various electrical components.
Recent events (2)
- — I (S) $2742.6
- — Z (S) $3918
1910.303 F02
- Issued
- Mar 28, 2024
- Abate by
- Apr 23, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2) - Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Location - 2nd Floor Electrical Room On or about 12/22/2023, breakers inside an electrical panel were not identified as to their purpose.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Cape Seafoods INC.
View Cape Seafoods INC.'s full OSHA safety record →
More inspections in this industry (NAICS 424460)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347184921.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.