OSHA Inspection: STAR ELECTRIC COMPANY OF TEXAS

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of STAR ELECTRIC COMPANY OF TEXAS in NAIL RANCH LEASE 36 1D, RRC #39517 32.128089, -102.018704, MIDLAND, TX 79701 (NAICS 237130). OSHA activity number 347188351.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Star Electric Company of Texas — free Get an email when a new federal OSHA severe-injury report for Star Electric Company of Texas is published. One employer, no account, unsubscribe in one click.
Site address
NAIL RANCH LEASE 36 1D, RRC #39517 32.128089, -102.018704
City
MIDLAND
State
TX
ZIP
79701
Mailing
PO BOX 4577, ODESSA, TX 79766
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
90
Ownership type
A

2 citations on file for this inspection.

1926.960 C01 III B

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
May 10, 2024
Abate by
Jun 10, 2024
Penalty
Initial $12,421 · Current $7,453 Reduced
29 CFR 1926.960(c)(1)(iii)(B): The energized part is insulated from the employee and from any other conductive object at a different potential    On or about January 2, 2024, employees engaged in power distribution construction at site Nail Ranch Lease 36 #1D, Midland, TX, were exposed to arc flash hazards as the employer did not ensure the energized lines or unenergized lines employees were working near had appropriate insulating cover while installing chemical grounds.
Recent events (2)
  • — I (O) $7452.6
  • — Z (S) $12421

1926.960 C02 I

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
May 10, 2024
Abate by
Jun 10, 2024
Penalty
Initial $12,421 · Current $7,453 Reduced
29 CFR  1926.960(c)(2)(i): When an employee uses rubber insulating gloves as insulation from energized parts (under paragraph (c)(1)(iii)(A) of this section), the employer shall ensure that the employee also uses rubber insulating sleeves.                                               On or about January 2, 2024, the employer did not ensure employees wore all appropriate personal protection equipment while working near energized parts of a power distribution line, exposing them to arc flash hazards.
Recent events (2)
  • — I (O) $7452.6
  • — Z (S) $12421

View Star Electric Company of Texas's full OSHA safety record →