MONACA, PA —
OSHA Inspection: BVPV STYRENICS LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BVPV STYRENICS LLC in 400 FRANKFORT ROAD, MONACA, PA 15061 (NAICS 325211). OSHA activity number 347190175.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BVPV STYRENICS LLC
- Site address
- 400 FRANKFORT ROAD
- City
- MONACA
- State
- PA
- ZIP
- 15061
- Mailing
- 400 FRANKFORT ROAD, MONACA, PA 15061
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325211
- Employees
- 186
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 E03 IV
- Issued
- Jun 27, 2024
- Abate by
- Aug 14, 2024
- Penalty
- Initial $9,334 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(e)(3)(iv): The process hazard analysis did not address the consequences of failure of engineering and administrative controls: a) D3 Tank Farm, BVPV Styrenics LLC, on or about January 3, 2024, the Process Hazard Analysis Polystyrene D3 Unit Styropek - Beaver Valley Site did not address the consequences of failure of the engineering and administrative controls for a loss of nitrogen to the East/North Tank (T-3398) and West/South Day Tank (T-3393). The controls include a conservation vent (PSV-3517) sized for inbreathing, a pressure transmitter (PAL-3W80) with a low alarm to prompt operator response, and a level transmitter (LAL-3N18) interlocked to stop the tank pump (P-3397) for the East/North Tank and a conservation vent (PSV-3502), a pressure transmitter (PAL-3W78), and a level transmitter (LAL-3N16) interlocked to stop the tank pump (P-3395) for the West/South Day Tank. b) D3 Polystyrene Process Area, BVPV Styrenics LLC, on or about January 3, 2024, the Process Hazard Analysis Polystyrene D3 Unit Styropek - Beaver Valley Site did not address the consequences of failure of the rupture discs (PSE-3157/8) discharging to atmosphere, agitator low amp alarm (IAL-3179) prompting operator response and interlocked to initiate cooling, temperature control (TIC-3321) to allow full cooling water flow on reactor jacket, manual valve (HV-3207) to allow transfer of reactor contents to a dump box, and pressure transmitter (PAH-3154) with alarm to prompt operator response for loss of agitation on polystyrene reactors. c) D3 Polystyrene Process Area, BVPV Styrenics LLC, on or about January 3, 2024, the Process Hazard Analysis Polystyrene D3 Unit Styropek - Beaver Valley Site did not address the consequences of failure of the dual mechanical seal on reactor 301 agitator (A-3193) and area LEL monitors with alarm for a loss of nitrogen on reactor M.O. Pots. d) D3 Expandable Polystyrene Process Area, BVPV Styrenics LLC, on or about January 3, 2024, the Process Hazard Analysis Expanded Polystyrene D3/D4 Units Styropek - Beaver Valley Site did not address the consequences of failure of the double mechanical seal on reactor agitator, level switch with alarm (LAL-3Y87) on the M.O. Pot to prompt operator response, exhaust fans in reactor building, and area LEL monitors with audible and visual alarms for a loss of nitrogen on reactor M.O. Pots. e) D3 Expandable Polystyrene Process Area, BVPV Styrenics LLC, on or about January 3, 2024, the Process Hazard Analysis Expanded Polystyrene D3/D4 Units Styropek - Beaver Valley Site did not address the consequences of failure of the ZSC-3Y37 opening for purge sequence to start, and area LEL monitors with audible and visual alarm for a loss of nitrogen during reactor purge. Not addressing the consequences of failure of engineering and administrative controls can expose employees to fire hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $9334
1910.119 F01 III A
- Issued
- Jun 27, 2024
- Abate by
- Aug 1, 2024
- Penalty
- Initial $9,334 · Current $7,400 Reduced
General-duty citation text
29 CFR 1910.119(f)(1)(iii)(A): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and did not address properties of, and hazards presented by, the chemicals used in the process: a) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures that provide properties of, and hazards presented by pentane and styrene in the written operating procedure 5.0, D3 Area Operators Manual, Safety Considerations/Operating Envelope/Consequences of Deviation. Failure to develop operating procedures that provide the properties and hazards presented by pentane and styrene can expose employees to chemical and physical hazards. b) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures that provide properties of, and hazards presented by pentane and styrene in the written operating procedure 5.0, D3 EPS Lead Operators Manual - D3 Safety Considerations/Operating Envelope/Consequences of Deviation. Failure to develop operating procedures that provide the properties and hazards presented by pentane and styrene can expose employees to chemical and physical hazards. c) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures that provide properties of, and hazards presented by pentane and styrene in the written operating procedure 5.0, D3 PS Lead Operators Manual - Safety Considerations. Failure to develop operating procedures that provide the properties and hazards presented by pentane and styrene can expose employees to chemical and physical hazards.
Recent events (2)
- — I (O) $7400
- — Z (S) $9334
1910.119 F01 III B
- Issued
- Jun 27, 2024
- Abate by
- Aug 1, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(f)(1)(iii)(B): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and did not address precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment: a) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures that address precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment in the written operating procedure 5.0, D3 Area Operators Manual - Safety Considerations/Operating Envelope/Consequences of Deviation. Failure to develop operating procedures that address precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment can expose employees to chemical and physical hazards. b) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures that address precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment in the written operating procedure 5.0, D3 EPS Lead Operators Manual - D3 Safety Considerations/Operating Envelope/Consequences of Deviation. Failure to develop operating procedures that address precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment can expose employees to chemical and physical hazards. c) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures that address precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment in the written operating procedure 5.0, D3 PS Lead Operators Manual - Safety Considerations. Failure to develop operating procedures that address precautions necessary to prevent exposure, including engineering controls, administrative controls, and personal protective equipment can expose employees to chemical and physical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 F01 III C
- Issued
- Jun 27, 2024
- Abate by
- Aug 1, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(f)(1)(iii)(C): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and did not address control measures to be taken if physical contact or airborne exposure occurs: a) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures in procedure 5.0, D3 Operators Manual - Safety Considerations/Operating Envelope/Consequences of Deviation that address control measures to be taken if physical contact or airborne exposure to pentane or styrene occurs. b) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures in procedure 5.0, D3 EPS Lead Operators Manual - D3 Safety Considerations/Operating Envelope/Consequences of Deviation that address control measures to be taken if physical contact or airborne exposure to pentane or styrene occurs. c) In the D3 Operating Area, on or about January 3, 2024 - The employer did not develop written operating procedures in procedure 5.0, D3 PS Lead Operating Procedures - Safety Considerations that address control measures to be taken if physical contact or airborne exposure to pentane or styrene occurs.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Bvpv Styrenics LLC
View Bvpv Styrenics LLC's full OSHA safety record →
More inspections in this industry (NAICS 325211)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347190175.