ARKADELPHIA, AR —
OSHA Inspection: VEOLIA NORTH AMERICA, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of VEOLIA NORTH AMERICA, INC. in 500 EAST REYNOLDS ROAD, ARKADELPHIA, AR 71923 (NAICS 562211). OSHA activity number 347205742.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VEOLIA NORTH AMERICA, INC.
- Site address
- 500 EAST REYNOLDS ROAD
- City
- ARKADELPHIA
- State
- AR
- ZIP
- 71923
- Mailing
- 500 EAST REYNOLDS ROAD, ARKADELPHIA, AR 71923
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 562211
- Employees
- 144
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.1450 E03 III
- Issued
- May 13, 2024
- Abate by
- Jun 7, 2024
- Penalty
- Initial $6,913 · Current $6,913
General-duty citation text
29 CFR 1910.1450(e)(3)(iii): The employer's Chemical Hygiene Plan did not include a requirement that fume hoods and other protective equipment functioned properly and did not include specific measures that would be taken to ensure proper and adequate performance of such equipment: a) On or about January 12, 2024, in the lab, employees analyzing organic vapors such as, but not limited to nitric acid and hydrogen chloride while using an operational fume hood that did not capture all fumes in that Hood 1 did not have a capture velocity of at least 100 feet per minute. On or about January 12, 2024, in the lab, employees engaged in analyzing organic vapors such as, but not limited to nitric acid and hydrogen chloride used a fume hood that was not incompliance with the hygiene plan in the following instances: b) Hood 1, the maximum sash opening was not measured and marked clearly and legibly at the working height; c) Hood 2, the maximum sash opening was not measured and marked clearly and legibly at the working height; d) Hood 3, the maximum sash opening was not measured and marked clearly and legibly at the working height; e) Air velocity measurements were taken annually instead of every six months; f) Records of the velocity readings for each hood were not maintained for comparison.
Recent events (2)
- — I (O) $6913
- — Z (S) $6913
More inspections at Veolia North America, INC.