Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GEORGIA-PACIFIC PANEL PRODUCTS, LLC

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of GEORGIA-PACIFIC PANEL PRODUCTS, LLC in 149 TEMPLE DRIVE, KANE, PA 16735 (NAICS 321219). OSHA activity number 347208217.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Georgia-Pacific Panel Products, LLC — free Get an email when a new federal OSHA severe-injury report for Georgia-Pacific Panel Products, LLC is published. One employer, no account, unsubscribe in one click.
Site address
149 TEMPLE DRIVE
City
KANE
State
PA
ZIP
16735
Mailing
149 TEMPLE DRIVE, KANE, PA 16735
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321219
Employees
109
Ownership type
A

1 citation on file for this inspection.

1910.176 C

Other-than-serious Gravity 1 1 instance 5 exposed
Issued
Feb 21, 2024
Abate by
Mar 18, 2024
Penalty
Initial $6,464 · Current $4,000 Reduced
1910.176(c) Storage areas were not kept free from accumulation of materials that constituted hazards from tripping, fire, explosion or pest harborage:  a)	Georgia-Pacific Panel Products, LLC, Dieffenbacher Press area, on or about January 10th, 2024, and times prior thereto:  Employees were potentially exposed to fire hazards in that, a wood dust "ball" accumulated in the "Platen and simultaneous arm" area of the Dieffenbacher Press after a press blow down procedure.  The employer did not establish a procedure for employees to verify that dust did not accumulate in areas including, but not limited to the Platen and simultaneous arm areas of the press after scheduled blow down procedures of the press.   b)	Georgia-Pacific Panel Products, LLC, on or about January 10th, 2024, and times prior thereto:  Employees were potentially exposed to fire hazards in that, combustible wood dust accumulated underneath the Dieffenbacher Press area (cylinder area) after a press blow down procedure.  The employer did not establish a procedure for employees to verify that dust did not accumulate underneath the Dieffenbacher Press area after scheduled blow down procedures of the press.   ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $4000
  • — Z (S) $6464

View Georgia-Pacific Panel Products, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347208217.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.