ATHENS, AL —
OSHA Inspection: DAY & ZIMMERMANN NPS, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of DAY & ZIMMERMANN NPS, INC. in NUCLEAR PLANT RD BROWNS FERRY NUCLEAR PLANT, ATHENS, AL 35611 (NAICS 238990). OSHA activity number 347262057.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DAY & ZIMMERMANN NPS, INC.
- Site address
- NUCLEAR PLANT RD BROWNS FERRY NUCLEAR PLANT
- City
- ATHENS
- State
- AL
- ZIP
- 35611
- Mailing
- 1500 SPRING GARDEN STREET, PHILADELPHIA, PA 19130
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238990
- Employees
- 437
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.333 A01
- Issued
- Jul 30, 2024
- Abate by
- Sep 6, 2024
- Penalty
- Initial $14,518 · Current $14,518
General-duty citation text
29 CFR 1910.333(a)(1): The employer failed to ensure that live parts were deenergized before employees began to work on or near live parts. (a) Unit 2 Reactor Building: On or about 2/01/2024, the employer exposed employees to arc flash and electrocution hazards, in that procedures were not utilized or enforced to ensure Temporary Power Unit was not deenergized prior to work and the cord energized at 480 V weas not under exclusive control of the crew. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
- — I (O) $14518
- — Z (S) $14518
1910.335 A01 I
- Issued
- Jul 30, 2024
- Abate by
- Sep 6, 2024
- Penalty
- Initial $14,518 · Current $14,518
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: (a) Unit 2 Reactor Building: On or about 2/01/2024, the employer exposed employees to arc flash and electrocution hazards, in that electrical protective equipment, such as but not limited to, 8 cal pants, 8 cal shirt with sleeves down, Arc Rated face shield or Flash Suit and hood were not used when disconnecting Temporary Power Unit cord energized at 480 V prior to relocating unit. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
- — I (O) $14518
- — Z (S) $14518
More inspections at DAY & Zimmermann NPS, INC.
View DAY & Zimmermann NPS, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238990)
More inspections in AL