OSHA Inspection: VALLEY POPCORN

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of VALLEY POPCORN in 6172 DIXIE ROAD, NEENAH, WI 54956 (NAICS 311919). OSHA activity number 347263295.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Valley Popcorn — free Get an email when a new federal OSHA severe-injury report for Valley Popcorn is published. One employer, no account, unsubscribe in one click.
Establishment
VALLEY POPCORN
Site address
6172 DIXIE ROAD
City
NEENAH
State
WI
ZIP
54956
Mailing
6172 DIXIE ROAD, NEENAH, WI 54956
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311919
Employees
30
Ownership type
A

6 citations on file for this inspection.

1910.157 C04

Serious Gravity 1 1 instance 3 exposed
Issued
May 22, 2024
Penalty
Initial $4,839 · Current $2,419 Reduced
29 CFR 1910.157(c)(4): The employer shall assure that portable fire extinguishers are maintained in a fully charged and operable condition and kept in their designated places at all times except during use.  On or about February 7, 2024, at the workplace located at 6172 Dixie Road, Neenah, Wisconsin: on Line 1, the employer did not ensure that a fire extinguisher was removed from service after extinguishing a fire and replaced, or that alternate equivalent protection was provided, exposing an employee to fire hazards.
Recent events (2)
  • — I (S) $2419
  • — Z (S) $4839

1910.157 E02

Serious Gravity 5 1 instance 12 exposed
Issued
May 22, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable extinguishers or hose used in lieu thereof under paragraph (d)(3) of this section shall be visually inspected monthly.  On or about February 7, 2024, at the workplace located at 6172 Dixie Road, Neenah, Wisconsin: the employer failed to ensure portable fire extinguishers were visually inspected monthly, exposing employees to potential thermal injuries.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C04 I

Serious Gravity 5 7 instances 9 exposed
Issued
May 22, 2024
Penalty
Initial $6,453 · Current $3,226 Reduced
29 CFR  1910.147(c)(4)(i):Procedures shall be developed, documented and utilized for the control of potentially hazardous energy when employees are engaged in the activities covered by this section.  On or about February 7, 2024, at the workplace located at 6172 Dixie Road, Neenah, Wisconsin: the employer did not develop and document energy control procedures.  a) The employer did not develop, document, and utilize energy control procedures for employees engaged in servicing and maintenance work such as, but not limited to, cleaning, jams, and set up for Canary Bagger (Serial: U19919, Model 12-19-HP).   b) The employer did not develop, document, and utilize energy control procedures for employees engaged in servicing and maintenance work such as, but not limited to, cleaning, jams, and set up for Line One.   c) The employer did not develop, document, and utilize energy control procedures for employees engaged in servicing and maintenance work such as, but not limited to, cleaning, jams, and set up for Line Two.  d) The employer did not develop, document, and utilize energy control procedures for employees engaged in servicing and maintenance work such as, but not limited to, cleaning, jams, and set up for Line Three.  e) The employer did not develop, document, and utilize energy control procedures for employees engaged in servicing and maintenance work such as, but not limited to, cleaning, jams, and set up for Line Four.  f) The employer did not develop, document, and utilize energy control procedures for employees engaged in servicing and maintenance work such as, but not limited to, preventive maintenance, change, adjust, and repair a part for Lantech Case erecting system (Serial: 20214388 Model: C-2000-Tape).  g) The employer did not develop, document, and utilize energy control procedures for employees engaged in servicing and maintenance work such as, but not limited to, preventive maintenance, change, adjust, and repair a part for Pearson Case erecting system (Serial: 2018CE3500272 Model: CE35-20T).   Note: Exception: The employer need not document the required procedure for a particular machine or equipment, when all of the following elements exist: (1) The machine or equipment has no potential for stored or residual energy or reaccumulation of stored energy after shut down which could endanger employees; (2) the machine or equipment has a single energy source which can be readily identified and isolated; (3) the isolation and locking out of that energy source will completely deenergize and deactivate the machine or equipment; (4) the machine or equipment is isolated from that energy source and locked out during servicing or maintenance; (5) a single lockout device will achieve a locker-out condition; (6) the lockout device is under the exclusive control of the authorized employee performing the servicing or maintenance; (7) the servicing or maintenance does not create hazards for other employees; and (8) the employer, in utilizing this exception, has had no accidents involving the unexpected activation or reenergization of the machine or equipment during servicing or maintenance.
Recent events (2)
  • — I (S) $3226
  • — Z (S) $6453

1910.147 C07 I

Serious Gravity 5 1 instance 9 exposed
Issued
May 22, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i): The employer shall provide training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of the energy controls are acquired by employees. The training shall include the following:  On or about February 7, 2024, at the workplace located at 6172 Dixie Road, Neenah, Wisconsin: the employer did not provide training to recognize all applicable hazardous energy sources as well as the means and methods to accomplish proper energy isolating steps exposing employees to accident or inadvertent restart of the equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Repeat Gravity 1 1 instance 3 exposed
Issued
May 22, 2024
Penalty
Initial $9,678 · Current $4,839 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure.   On or about February 7, 2024, at the workplace located at 6172 Dixie Road, Neenah, Wisconsin: the employer was utilizing an extension cord to power a seed dispenser on line one instead of fixed wiring.  Valley Popcorn was previously cited for a violation of this occupational safety and health standard or its equivalent standard (29 CFR 1910.305(g)(1)(iv)(A): which was contained in OSHA inspection number 1385006, citation number 1, item number 4/c and was affirmed as a final order on September 5,2019, with respect to a workplace located at 6172 Dixie Road, Neenah, Wisconsin.
Recent events (2)
  • — I (R) $4839
  • — Z (R) $9678

1910.305 B01 I

Other-than-serious 2 instances 6 exposed
Issued
May 22, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed.   At an establishment located at 6172 Dixie Road, Neenah, Wisconsin:  On or about February 7, 2024, at the workplace located at 6172 Dixie Road, Neenah, Wisconsin: electrical cables entering junction boxes were not protected from abrasions, exposing employees to potential contact with energized electrical parts in case the cables insulation is damaged.  a) On or about February 7, 2024, on Line 1 Motor (Serial: F1404222752) the conduit was pulled exposing wires to abrasion while employees were operating while being exposed to electrical shock hazards.  b) On or about February 7, 2024, on Line 2 Speed Control Genesis the conduit was pulled exposing wires to abrasion while employees were operating while being exposed to electrical shock hazards.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Valley Popcorn's full OSHA safety record →