RIVERSIDE, CA —
OSHA Inspection: BUREAU OF INDIAN EDUCATION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BUREAU OF INDIAN EDUCATION in 9010 MAGNOLIA AVENUE, RIVERSIDE, CA 92503 (NAICS 611110). OSHA activity number 347275539.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUREAU OF INDIAN EDUCATION
- Site address
- 9010 MAGNOLIA AVENUE
- City
- RIVERSIDE
- State
- CA
- ZIP
- 92503
- Mailing
- 9010 MAGNOLIA AVENUE, RIVERSIDE, CA 92503
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 611110
- Employees
- 94
- Ownership type
- D
Citations
20 citations on file for this inspection.
1910.36 D03
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(d)(3): An exit route door may be locked from the inside only in mental, penal, or correctional facilities and then only if supervisory personnel are continuously on duty and the employer has a plan to remove occupants from the facility during an emergency. On and/or before February 8th, 2024, exit route doors were locked from the inside. This conditions potentially exposed employee(s) to delayed egress, fire, and/ smoke inhalation hazard(s). In the following locations: a) Building 10, Ramona Dorm, Laundry Room (128), locked exit door. b) Building 3, Wigwam dorm, West end, Room (128) locked exit door. c) Building 6, Winona Dorm, North end, Room (128) locked exit door.
Recent events (1)
- — Z (S) $0
1910.37 A04
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: On and/or before February 8th, 2024, safeguards designed to protect employee(s) during an emergency were not in proper working order at all times. This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) Ramona building 10, Basement, Missing Ceiling tiles throughout hallway and adjacent rooms. b) Wigwam building 3, Basement, i) Missing Ceiling tiles throughout hallway and adjacent rooms. ii) Rm 101 multiple escutcheons not installed. iii) Ceiling tiles missing outside Rm 126. c) Winona building 6, i) Rm 002, hole located on top righthand of fire wall door. ii) Missing Ceiling tiles throughout hallway and adjacent rooms. iii) multiple fire sprinkler head face plates not installed between rooms 109-120 and 141-152. d) Building 60, outside Rm 153 fire sprinkler face plate not installed.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Jul 12, 2024
- Abate by
- Aug 21, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": On and/or before February 8, 2024, multiple exit(s) in the dorm were not marked with a sign reading "exit". This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) Building 3, Wigwam Dorm: Main entrance b) Building 3, Wigwam Dorm: Double exit doors between room 101-102 c) Building 3, Wigwam Dorm: Laundry room 127 d) Building 3, Wigwam Dorm: West End double doors next to basement stairs e) Building 10, Ramona Dorm: Laundry room 127
Recent events (1)
- — Z (S) $0
1910.37 A03
- Issued
- Jul 12, 2024
- Abate by
- Aug 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: Building 6, Winona Dorm, Laundry Room (128): On and/or before February 8, 2024, the employer did not ensure that an emergency exit in Rm 128 was kept free and unobstructed by a large grey garbage can. Employee(s) were potentially exposed to fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.157 C01
- Issued
- Jul 12, 2024
- Abate by
- Aug 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. Building 10, Ramona Dorm, Basement: On and/or before February 8, 2024, portable fire extinguishers for employee use was not mounted without subjecting the employee(s) to injuries. Employee(s) were potentially exposed to struck-by-hazard(s).
Recent events (1)
- — Z (S) $0
1910.157 E03
- Issued
- Jul 12, 2024
- Abate by
- Jul 31, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: On and/or before February 9, 2024, fire extinguisher(s) mounted/staged were not up to date with their annual maintenance check. This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) Building 60 b) Wigwam Dorm, Bldg. 3 c) Ramona Dorm, Bldg. 10 d) Winona, Bldg. 6 e) Cafeteria, Bldg. 9
Recent events (1)
- — Z (S) $0
1910.159 C02
- Issued
- Jul 12, 2024
- Abate by
- Dec 6, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(2): The employer did not properly maintain the installed automatic sprinkler system. The employer shall assure that a main drain flow test is performed on each system annually. The inspector's test valve shall be opened at least every two years to assure that the sprinkler system operates properly. On and/or before February 8, 2024, the employer did not properly maintain or inspect the installed automatic sprinkler system. This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) Building 60 b) Ramona, building 10 c) Winona, building 6 d) Wigwam, building 3
Recent events (2)
- — P (S) $0
- — Z (S) $0
1910.160 B09
- Issued
- Jul 12, 2024
- Abate by
- Aug 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.160(b)(9): Inspection and maintenance dates of fixed extinguishing systems were not recorded on the container, on a tag attached to the container, or in a central location: Cafeteria, Bldg. 9: On and/or before February 08, 2024, employee(s) used various kitchen appliances to prepare food for students. A record of the annual check of the Casco Automatic Dry Chemical fire suppression system was not maintained since May 2021. Employee(s) were exposed to fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.165 D01
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.165(d)(1): Employee alarm systems were not maintained in operating condition: On and/or before February 8, 2024, alarm systems were not maintained in operating conditions. This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) Building 60 b) Wigwam Dorm, Bldg. 3 c) Ramona Dorm, Bldg. 10 d) Winona, Bldg. 6 e) Cafeteria, Bldg. 9 f) Facilities Bldg. 67
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Jul 12, 2024
- Abate by
- Aug 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On and/or before February 8, 2024, multiple appliances/ machines such as a refrigerator, microwave, and heater were plugged into a relocatable power tap in which were not used according to listing and labeling instructions. This condition potentially exposed employee(s) to electrical and fire hazard(s). In the following locations: a) Winona Bldg. 6, Break room, an RCA surge protector was used to power a Keurig coffee maker, Bella toaster, and a General Electric refrigerator/ freezer. b) Ramona Bldg. 10, Rm 160, a Ceramic Tower Heater model number HFX25S15L was plugged into a relocatable power tap. c) Wigwam Bldg. 3, Break room, a Keurig coffee maker, west bend microwave, and Chefman water heater were plugged into a black extension cord. d) Cafeteria Bldg. 9, Manager office, a Lasko Tower Heater was not used in accordance with listing or labeling.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On and/or before February 9, 2024, the labeling inside multiple panel boxes that listed the purpose of each disconnecting device was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. This condition possibly exposed employee(s) to electrical and/or fire hazard(s). In the following locations: a) Wigwam, main hallway across rm 129 b) Wigwam, room 128 c) Wigwam, room 129 d) Ramona, room 139 e) Ramona, Room 122 f) Winona, room 122 g) Winona, room 136
Recent events (1)
- — Z (S) $0
1910.303 G01 II
- Issued
- Jul 12, 2024
- Abate by
- Jul 31, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Building 3, Wigwam Dorm, Room 129: On and/or before February 12, 2024, a laundry basket was placed within 36 inches of the circuit breaker panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.305 A02 IX
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lamp holder with a guard. Cafeteria, main kitchen, above the Baker Pride Oven: On and/or before February 8, 2024, three lamps above the Bakers pride oven were not protected from accidental contact by a suitable cover. This condition potentially exposed employee(s) to fire and electrical hazard(s).
Recent events (1)
- — Z (S) $0
1910.305 A02 X
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points: Winona Room 140-141: On and/or before February 8th, 2024, an Airrex Model: AHSC-14 portable heat pump next to room 140 was plugged into a green extension which was run along the ceiling to room 140 and through the doorway. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Jul 12, 2024
- Abate by
- Aug 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Building 9, West End Wall Main Dining Hall: On and/or before February 8, 2024, the employer had not effectively covered 3 outlet boxes. This condition potentially exposed employees to electrical and/or fire hazards.
Recent events (1)
- — Z (S) $0
1910.332 B01
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Wigwam Bldg. 3: On and/or before February 12, 2024, Employee(s) were engaged in electrical-related work, including but not limited to, installing outlets and trouble-shooting electrical wiring. Employee(s) performed electrical-related work without being provided training on electrical safety-related work practices. Employee(s) are exposed to electrical shock hazards over 50 volts.
Recent events (1)
- — Z (S) $0
1910.333 B02 V A
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(v)(A): A qualified person did not conduct tests and visual inspections, as necessary, to verify that all tools, electrical jumpers, shorts, grounds, and other such devices had been removed, so that the circuits and equipment could be safely energized. Wigwam dorm: On and/or before February 8, 2024, an employee was tasked to replace an outlet in room 126. A qualified person did not conduct tests and visual inspections to verify that all shorts and grounds had been removed so that the circuits and equipment could be safely energized. Employee(s) were potentially exposed to electrical shock and/or arc flash hazard(s).
Recent events (1)
- — Z (S) $0
1910.334 B02
- Issued
- Jul 12, 2024
- Abate by
- Aug 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(b)(2): The repetitive manual reclosing of circuit breakers or reenergizing electric power and lighting circuits through replaced fuses was not prohibited: On and/or before February 8th, 2024, the employer did not prohibit employee(s) from reclosing circuit breakers repetitively in the event of a trip due to an overload in the circuit. Employee(s) were potentially exposed to electrical shock and/or fire hazard(s). In the following locations: a) Ramona Bldg. 10 b) Winona Bldg. 6
Recent events (1)
- — Z (S) $0
1960.66 B
- Issued
- Jul 12, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.66(b): Federal agency injury and illness recording and reporting shall comply with the requirements under 29 CFR 1904, subparts C, D, E, and G, except that the definition of "establishment" found in 29 CFR 1960.2(h) will remain applicable to Federal agencies. 29 CFR 1904.40(a) reference: The employer had not provided an authorized government representative the records within the four business hours. Sherman Indian High School: On February 8, 2024, the employer failed to provide copies of the requested injury and illness records for the calendar years 2021, 2022, 2023 when requested both verbally and in writing. The Bureau of Indian Education was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1960.66(b), which was contained in OSHA inspection number 1546996, citation number 2, item number 1, issued on January 19, 2021, which was affirmed as a final order on March 12, 2012 with respect to a workplace located at Tuba City Boarding School, Tuba City, Arizona 86045.
Recent events (1)
- — Z (R) $0
1910.303 B07 IV
- Issued
- Jul 12, 2024
- Abate by
- Aug 21, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. Wigwam building 3, room 128: On and/or before February 8, 2024, the top hinge of the circuit breaker panel door was broken. This condition may adversely affect the safe operation of the panel. Employee(s) were potentially exposed to a struck-by-hazard.
Recent events (1)
- — Z (O) $0
More inspections at Bureau of Indian Education
View Bureau of Indian Education's full OSHA safety record →
More inspections in this industry (NAICS 611110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347275539.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.