OSHA Inspection: RWE CLEAN ENERGY SERVICES, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of RWE CLEAN ENERGY SERVICES, LLC in ROSCOE WIND TURBINE 169, ROSCOE, TX 79545 (NAICS 221115). OSHA activity number 347337073.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch RWE Clean Energy Services, LLC — free Get an email when a new federal OSHA severe-injury report for RWE Clean Energy Services, LLC is published. One employer, no account, unsubscribe in one click.
Site address
ROSCOE WIND TURBINE 169
City
ROSCOE
State
TX
ZIP
79545
Mailing
1401 E 6TH ST SUITE 400, AUSTIN, TX 78702
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221115
Employees
10
Ownership type
A

5 citations on file for this inspection.

1910.147 C06 II

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Jun 25, 2024
Abate by
Aug 30, 2024
Penalty
Initial $13,828 · Current $27,656
29 CFR  1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed:   On or about the 4th of March 2024, at Roscoe  Wind Turbine 169, the employer failed to certify periodic inspections of employees performing servicing and maintenance activities on wind towers including, but not limited to, capacitor(s) which had stored electric as its energy source.
Recent events (2)
  • — I (O) $27656
  • — Z (S) $13828

1910.333 B02 II C

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jun 25, 2024
Abate by
Jul 24, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(ii)(C): Stored electric energy which might endanger personnel was not released.  Capacitors were not discharged and high capacitance elements were not short-circuited and grounded.  On or about the 4th of March 2024, at wind turbine tower; the employer did not require the high capacitance elements to be short circuited and grounded prior to employees working inside the component gear box to repair component(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02 IV B

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Jun 25, 2024
Abate by
Aug 30, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.333(b)(2)(iv)(B):Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that  On or about the 4th of March 2024,  in Roscoe  Wind Turbine 169, the employer failed to confirm pre-testing the electrical circuits and parts via testing equipment, prior to working as de-energized equipment, as employees worked to replace component(s) within tower.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.333 B02 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jun 25, 2024
Abate by
Jul 24, 2024
Penalty
Initial $13,828 · Current $0 Reduced
29 CFR  1910.333(b)(2)(i):The employer did not make a written copy of the procedures outlined in paragraph (b)(2) of 29 CFR 1910.333 available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:  On or about the 4th of March 2024, The employer provided a generic LOTO plan, but it was not specific to the task being performed by employees
Recent events (2)
  • — I (S) $0
  • — Z (S) $13828

1910.333 B02 II A

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Jun 25, 2024
Abate by
Aug 30, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.333(b)(2)(ii)(A):Safe procedures for deenergizing circuits and equipment were not determined before circuits or equipment are deenergized.  On or about the 4th of March 2024, in Roscoe  Wind Turbine 169, the employer did not ensure employees were provided procedures for deenergizing component(s) in and around gearbox prior to starting task.