OSHA Inspection: OREGON AIR NATIONAL GUARD - 142 WING

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of OREGON AIR NATIONAL GUARD - 142 WING in 6801 NE CORNFOOT RD, PORTLAND, OR 97218 (NAICS 928110). OSHA activity number 347367278.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Oregon AIR National Guard - 142 Wing — free Get an email when a new federal OSHA severe-injury report for Oregon AIR National Guard - 142 Wing is published. One employer, no account, unsubscribe in one click.
Site address
6801 NE CORNFOOT RD
City
PORTLAND
State
OR
ZIP
97218
Mailing
6801 NE CORNFOOT RD, PORTLAND, OR 97218
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
215
Ownership type
D

4 citations on file for this inspection.

1910.178 G02

Serious Gravity 5 1 instance 5 exposed
Issued
May 13, 2024
Abate by
Jun 7, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.178(g)(2): Battery charging apparatus for industrial trucks located in battery changing and charging installation was not protected from damage by trucks:  (a)at 6801 NE Cornfoot Road, Portland, Oregon 97218,LRS Warehouse on or about 21 March 2024 and at times prior thereto: Employer failed to guard battery charging apparatuses from damage by trucks, exposing employees to potential electrical burns, shock, and flash arc from 208 volt supply source.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 3 exposed
Issued
May 13, 2024
Abate by
Jun 7, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2):Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling.  (a)at 6801 NE Cornfoot Road, Portland, Oregon 97218, Bldg. 142, MSG office on or about 21 March 2024 and at times prior thereto: Employees were exposed to fire and electrical shock  hazardous condition from a Relocatable power taps (power strips) were series-connected (daisy-chained) to extension cords or other power strips resulting in minor burns and electrical shock.   For Reference:  Underwriters Laboratories (UL), refers to power strips as Relocatable Power Taps (RPTs) and, in its "General Information for Electrical Equipment Directory" (sometimes called the UL white book or UL Directory) contains instructions that require UL-listed RPTs to be directly connected to a permanently installed branch circuit receptacle; they are not to be series-connected to other RPTs or connected to extension cords.
Recent events (1)
  • — Z (S) $0

1910.37 A04

Other-than-serious 2 instances 5 exposed
Issued
May 13, 2024
Abate by
Jun 7, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.37(a)(4):Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:  (a)at 6801 NE Cornfoot Road, Portland, Oregon 97218,LRS Warehouse office, Vehicle Maintenance West bay, on or about 21 March 2024 and at times prior thereto: Employees were exposed to fall/trip hazards  from exit route emergency light not operating properly which would impair employee vision in the event of an emergency, resulting in injuries, bruises, and minor disabilities.
Recent events (1)
  • — Z (O) $0

1910.303 G01

Other-than-serious 1 instance 1 exposed
Issued
May 13, 2024
Abate by
Jun 7, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  (a)at 6801 NE Cornfoot Road, Portland, Oregon 97218,LRS Warehouse on or about 21 March 2024 and at times prior thereto: Employees were exposed to fire/electrical burns caused by a blocked electrical control panel. resulting in serious burns, shock, and/or fire while trying to access component to service/maintain.
Recent events (1)
  • — Z (O) $0

View Oregon AIR National Guard - 142 Wing's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347367278.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.