1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: G-FORM, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of G-FORM, LLC in 1 TUPPERWARE DRIVE, NORTH SMITHFIELD, RI 02896 (NAICS 315990). OSHA activity number 347369910.

Watch G-Form, LLC — free Get an email when a new federal OSHA severe-injury report for G-Form, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
G-FORM, LLC
Site address
1 TUPPERWARE DRIVE
City
NORTH SMITHFIELD
State
RI
ZIP
02896
Mailing
139 POINT STREET, PROVIDENCE, RI 02903
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
315990
Employees
15
Ownership type
A

7 citations on file for this inspection.

1910.147 C06 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $5445.00 · Current $2723.00 Reduced
29 CFR  1910.147(c)(6)(i): The employer did not conduct an annual or more frequent inspection of the energy control procedure to ensure that the procedure and requirements of this standard were followed:   a) Establishment: On or about March 26, 2024, employees were exposed to energy source hazards due to the employer's failure to conduct an annual review of their lockout/tagout (LOTO) procedures to ensure that the procedures and requirements of this standard were followed.
Recent events (2)
  • — I (S) $2722.5
  • — Z (S) $5445

1910.147 D04 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.147(d)(4)(i): Lockout or tagout devices were not affixed to each energy isolating device by authorized employees:   a) Small Production Machine: On or about March 26, 2024, employees were exposed to machine operation hazards when maintance was being performed on the equipment which was not effectively provided with lockout or tagout of each energy source.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph:   a) Small Production Machine: On or about March 26, 2024, employees were exposed to electrical shock of 208 Volts and arc fault hazards while working on an electrical cabinet operating the Small Production Machine, whose energy source had not been locked and/or tagged out properly during servicing and maintenance activities.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $5445.00 · Current $2723.00 Reduced
29 CFR  1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:  a) Small Production Machine: On or about March 26, 2024, employees were exposed to electrical shock and arc fault hazards due to an electrical cabinet operating the Small Production Machine with a hinged door that was not closed and properly guarded.
Recent events (2)
  • — I (S) $2722.5
  • — Z (S) $5445

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or was near to them:   a) Small Production Machine: On or about March 26, 2024, employees were exposed to electrical shock and arc fault hazards within an electrical cabinet operating the Small Production Machine that was not adequately deenergized, to include testing with electrical equipment to confirm that it was deenergized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.335 B

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.335(b): No alerting techniques were used to warn and protect employees from hazards which could cause injury due to electric shock, burns, or failure of electric equipment:   a) Small Production Machine: On or about March 26, 2024, employees were exposed to electrical shock and arc fault hazards when work was being performed on an electrical cabinet operating the Small Production Machine that was not adequately barricaded and labeled to alert employees of the hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV A

Other-than-serious 4 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   a) Sheeting Machine: On or about March 26, 2024, employees were exposed to electrical hazards due to an extension cord being used on a permanent basis to provide 120 Volt power to a light fixture on the Sheeting Machine.  b) Pad Printers: On or about March 26, 2024, employees were exposed to electrical hazards due to an extension cord being used on a permanent basis to provide 120 Volt power to the three Pad Printers.  c) Small Production Machine: On or about March 26, 2024, employees were exposed to electrical hazards due to an extension cord being used on a permanent basis to provide 120 Volt power to the Small Production Machine.  d) Heat Press #1: On or about March 26, 2024, employees were exposed to electrical hazards due to an extension cord being used on a permanent basis to provide 120 Volt power to the air compressor for Heat Press Machine #1.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View G-FORM, LLC's full OSHA safety record →