KODIAK, AK —
OSHA Inspection: DEFENSE COMMISSARY AGENCY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEFENSE COMMISSARY AGENCY in USCG BLDG. N-27 B AVENUE, KODIAK, AK 99619 (NAICS 445110). OSHA activity number 347460271.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEFENSE COMMISSARY AGENCY
- Site address
- USCG BLDG. N-27 B AVENUE
- City
- KODIAK
- State
- AK
- ZIP
- 99619
- Mailing
- P.O. BOX 195028, KODIAK, AK 99619
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 25
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.37 A03
- Issued
- Jun 18, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) Locker Room: On or about April 30, 2024, produce and shopping carts were stored in front of and within the route of an exit door, exposing employees to fire hazards.
Recent events (1)
- — Z (O) $0
1910.37 B01
- Issued
- Jun 18, 2024
- Abate by
- Jul 1, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not equipped with operable lighting that to allow employees, with normal vision, to see along the exit route. a) Main Admin Office: On or about April 30, 2024 emergency lightening equipped with an exit sign did not light when tested, exposing employees to fire hazards.
Recent events (1)
- — Z (O) $0
1910.303 G01 I B
- Issued
- Jun 18, 2024
- Abate by
- Jul 1, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : a) Conference Room: On or about April 30, 2024, a large printer was obstructing an electrical panel, exposing employees to electrical hazards.
Recent events (1)
- — Z (O) $0
More inspections at Defense Commissary Agency