Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BUREAU OF LAND MANAGEMENT, MEDFORD DISTRICT OFFICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUREAU OF LAND MANAGEMENT, MEDFORD DISTRICT OFFICE in 3040 BIDDLE ROAD, MEDFORD, OR 97504 (NAICS 924120). OSHA activity number 347473498.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bureau of Land Management, Medford District Office — free Get an email when a new federal OSHA severe-injury report for Bureau of Land Management, Medford District Office is published. One employer, no account, unsubscribe in one click.
Site address
3040 BIDDLE ROAD
City
MEDFORD
State
OR
ZIP
97504
Mailing
3040 BIDDLE ROAD, MEDFORD, OR 97504
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
181
Ownership type
D

2 citations on file for this inspection.

1910.37 A04

Other-than-serious 5 instances 146 exposed
Issued
May 29, 2024
Abate by
Jun 25, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times.  (a) Room I-020, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event.  (b)Engineering section, near plotter, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event.  (c) First floor restroom, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event.  (d) Building back exit, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event.  (e) Room 2-124, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event.
Recent events (1)
  • — Z (O) $0

1910.303 B02

Other-than-serious 3 instances 181 exposed
Issued
May 29, 2024
Abate by
Jun 25, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.303 (b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling.   (a) Coo conference room, on May 9, 2024, and at times prior thereto: Employees were exposed to fire and electrical shock hazardous condition from a Relocatable power tap (power strips) were series-connected (daisy-chained) to extension cords or other power strips resulting in minor burns and electrical shock.   (b) Gym area, on May 9, 2024, and at times prior thereto: Employees were exposed to fire and electrical shock hazardous condition from a Relocatable power tap (power strips) were series-connected (daisy-chained) to extension cords or other power strips resulting in minor burns and electrical shock.   (c) Office 2-013, on May 9, 2024, and at times prior thereto: Employees were exposed to fire and electrical shock hazardous condition from a Relocatable power tap (power strips) were series-connected (daisy-chained) to extension cords or other power strips resulting in minor burns and electrical shock.   For Reference:  Underwriters Laboratories (UL) refers to power strips as Relocatable Power Taps (RPTs) and, in its "General Information for Electrical Equipment Directory" (sometimes called the UL white book or UL Directory) contains instructions that require UL-listed RPTs to be directly connected to a permanently installed branch circuit receptacle; they are not to be series-connected to other RPTs or connected to extension cords.             Equipment:            120-volt 15-amp Relocatable Power Tap           Condition:               A relocatable power tap that is designed to be plugged into a branch circuit was connected to a 120-volt 15-amp 14-gauge extension cord.