MEDFORD, OR —
OSHA Inspection: BUREAU OF LAND MANAGEMENT, MEDFORD DISTRICT OFFICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUREAU OF LAND MANAGEMENT, MEDFORD DISTRICT OFFICE in 3040 BIDDLE ROAD, MEDFORD, OR 97504 (NAICS 924120). OSHA activity number 347473498.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUREAU OF LAND MANAGEMENT, MEDFORD DISTRICT OFFICE
- Site address
- 3040 BIDDLE ROAD
- City
- MEDFORD
- State
- OR
- ZIP
- 97504
- Mailing
- 3040 BIDDLE ROAD, MEDFORD, OR 97504
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 181
- Ownership type
- D
Citations
2 citations on file for this inspection.
1910.37 A04
- Issued
- May 29, 2024
- Abate by
- Jun 25, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times. (a) Room I-020, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event. (b)Engineering section, near plotter, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event. (c) First floor restroom, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event. (d) Building back exit, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event. (e) Room 2-124, on or about 9 May 2024 and at times thereof: Employees were exposed to an exit route path lighting that is not operational. Resulting in trip/fall and burn injuries from trying to exit building during an emergency event.
Recent events (1)
- — Z (O) $0
1910.303 B02
- Issued
- May 29, 2024
- Abate by
- Jun 25, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303 (b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. (a) Coo conference room, on May 9, 2024, and at times prior thereto: Employees were exposed to fire and electrical shock hazardous condition from a Relocatable power tap (power strips) were series-connected (daisy-chained) to extension cords or other power strips resulting in minor burns and electrical shock. (b) Gym area, on May 9, 2024, and at times prior thereto: Employees were exposed to fire and electrical shock hazardous condition from a Relocatable power tap (power strips) were series-connected (daisy-chained) to extension cords or other power strips resulting in minor burns and electrical shock. (c) Office 2-013, on May 9, 2024, and at times prior thereto: Employees were exposed to fire and electrical shock hazardous condition from a Relocatable power tap (power strips) were series-connected (daisy-chained) to extension cords or other power strips resulting in minor burns and electrical shock. For Reference: Underwriters Laboratories (UL) refers to power strips as Relocatable Power Taps (RPTs) and, in its "General Information for Electrical Equipment Directory" (sometimes called the UL white book or UL Directory) contains instructions that require UL-listed RPTs to be directly connected to a permanently installed branch circuit receptacle; they are not to be series-connected to other RPTs or connected to extension cords. Equipment: 120-volt 15-amp Relocatable Power Tap Condition: A relocatable power tap that is designed to be plugged into a branch circuit was connected to a 120-volt 15-amp 14-gauge extension cord.
Recent events (1)
- — Z (O) $0
More inspections at Bureau of Land Management, Medford District Office
View Bureau of Land Management, Medford District Office's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347473498.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.