OSHA Inspection: U.S. MARSHALS SERVICE, WESTERN DIVISION/ TACOMA

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of U.S. MARSHALS SERVICE, WESTERN DIVISION/ TACOMA in 1717 PACIFIC AVENUE SUITE 1170, TACOMA, WA 98402 (NAICS 922120). OSHA activity number 347545873.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Marshals Service, Western Division/ Tacoma — free Get an email when a new federal OSHA severe-injury report for U.S. Marshals Service, Western Division/ Tacoma is published. One employer, no account, unsubscribe in one click.
Site address
1717 PACIFIC AVENUE SUITE 1170
City
TACOMA
State
WA
ZIP
98402
Mailing
1717 PACIFIC AVENUE SUITE 1170, TACOMA, WA 98402
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922120
Employees
5
Ownership type
D

4 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 3 instances 5 exposed
Issued
Jun 26, 2024
Abate by
Dec 13, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) Office Suite, where relocatable power taps (surge protectors) not used as listed and labeled included:  1. IT Room 9208, where the relocatable power tap located adjacent to the computer rack was permanently attached to the wall.  2. IT Room 9208, where the relocatable power tap located adjacent to the entry door was permanently attached to the wall.  3. Office Suite Entry, where an orange extension cord was daisy chained with a relocatable power tap and used to supply power to the surveillance monitor.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 3 instances 5 exposed
Issued
Jun 26, 2024
Abate by
Dec 13, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Office Suite, where flexible cords used as a substitute for fix wiring included:  1. IT Room 9208, where an orange extension cord was used to supply power to electronic equipment located in the Courtside Radio System Repeater metal cage.  2. IT Room 9208, where an orange extension cord was used to supply power to computer equipment located in the metal computer rack.  3. Office Suite Entry, where an orange extension cord was used to supply power to the surveillance monitor.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 3 instances 5 exposed
Issued
Jun 26, 2024
Abate by
Dec 13, 2024
Penalty
Initial $0 · Current $0
1910.305(g)(1)(iv)(B):  Flexible cords and cables were run through holes in walls, ceilings, or floors:  a) Office Suite, where energized orange extension cords run through the ceiling included:   1. IT Room 9208, where the orange extension cord used to supply power to electronic equipment located in the Courtside Radio System Repeater metal cage was run through the ceiling.  2. Office Suite Entry, where the orange extension cord was run through the ceiling and used to supply power to the relocatable power tap that the surveillance monitor was plugged into.  3. Office Suite Entry, where the power cord on the relocatable power tap used to supply power to the surveillance monitor was run through the ceiling.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 1 1 instance 5 exposed
Issued
Jun 26, 2024
Abate by
Dec 13, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces:  a) IT Room 9208, where the orange extension cord used to supply power to electronic equipment located in the Courtside Radio system Repeater metal cage was fastened to the wall.
Recent events (1)
  • — Z (S) $0

View U.S. Marshals Service, Western Division/ Tacoma's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347545873.