TACOMA, WA —
OSHA Inspection: U.S. MARSHALS SERVICE, WESTERN DIVISION/ TACOMA
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of U.S. MARSHALS SERVICE, WESTERN DIVISION/ TACOMA in 1717 PACIFIC AVENUE SUITE 1170, TACOMA, WA 98402 (NAICS 922120). OSHA activity number 347545873.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. MARSHALS SERVICE, WESTERN DIVISION/ TACOMA
- Site address
- 1717 PACIFIC AVENUE SUITE 1170
- City
- TACOMA
- State
- WA
- ZIP
- 98402
- Mailing
- 1717 PACIFIC AVENUE SUITE 1170, TACOMA, WA 98402
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 922120
- Employees
- 5
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Jun 26, 2024
- Abate by
- Dec 13, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Office Suite, where relocatable power taps (surge protectors) not used as listed and labeled included: 1. IT Room 9208, where the relocatable power tap located adjacent to the computer rack was permanently attached to the wall. 2. IT Room 9208, where the relocatable power tap located adjacent to the entry door was permanently attached to the wall. 3. Office Suite Entry, where an orange extension cord was daisy chained with a relocatable power tap and used to supply power to the surveillance monitor.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jun 26, 2024
- Abate by
- Dec 13, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Office Suite, where flexible cords used as a substitute for fix wiring included: 1. IT Room 9208, where an orange extension cord was used to supply power to electronic equipment located in the Courtside Radio System Repeater metal cage. 2. IT Room 9208, where an orange extension cord was used to supply power to computer equipment located in the metal computer rack. 3. Office Suite Entry, where an orange extension cord was used to supply power to the surveillance monitor.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Jun 26, 2024
- Abate by
- Dec 13, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors: a) Office Suite, where energized orange extension cords run through the ceiling included: 1. IT Room 9208, where the orange extension cord used to supply power to electronic equipment located in the Courtside Radio System Repeater metal cage was run through the ceiling. 2. Office Suite Entry, where the orange extension cord was run through the ceiling and used to supply power to the relocatable power tap that the surveillance monitor was plugged into. 3. Office Suite Entry, where the power cord on the relocatable power tap used to supply power to the surveillance monitor was run through the ceiling.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Jun 26, 2024
- Abate by
- Dec 13, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: a) IT Room 9208, where the orange extension cord used to supply power to electronic equipment located in the Courtside Radio system Repeater metal cage was fastened to the wall.
Recent events (1)
- — Z (S) $0
More inspections at U.S. Marshals Service, Western Division/ Tacoma
View U.S. Marshals Service, Western Division/ Tacoma's full OSHA safety record →