OSHA Inspection: ARCHER-DANIELS-MIDLAND COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ARCHER-DANIELS-MIDLAND COMPANY in 809 SPANGLER ROAD, CAMP HILL, PA 17011 (NAICS 311211). OSHA activity number 347649956.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Archer-Daniels-Midland Company — free Get an email when a new federal OSHA severe-injury report for Archer-Daniels-Midland Company is published. One employer, no account, unsubscribe in one click.
Site address
809 SPANGLER ROAD
City
CAMP HILL
State
PA
ZIP
17011
Mailing
4666 FARIES PARKWAY, DECATUR, IL 62525
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311211
Employees
73
Ownership type
A

4 citations on file for this inspection.

1910.37 B06

Other-than-serious Gravity 1 3 instances 15 exposed
Issued
Dec 9, 2024
Penalty
Initial $6,464 · Current $4,000 Reduced
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  a. Administration Building - On or about July 30, 2024, the exit signs throughout the administration building were metal signs that did not have emergency lighting and were not self-illuminating or designed to be photoluminescent.  b. Maintenance Shop - On or about November 8, 2024, the exit sign leading from the maintenance shop to the outside of the building was no self-illuminating or provided with alternative emergency illumination.  c. Mill exit to maintenance shop - On or about November 8, 2024, the exit sign leading from the mill into the maintenance shop for discharge from the maintenance shop to the exterior was not illuminated or provided with alternative emergency lighting.    Corrected During Inspection
Recent events (3)
  • — F (O) $4000
  • — C (S) $6464
  • — Z (S) $6464

1910.119 C02

Deleted Other-than-serious 1 instance 13 exposed
Issued
Dec 9, 2024
Abate by
Dec 23, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.119(c)(2): The employer did not consult with employees and their representatives on the conduct and development of process hazards analyses (PHA) and on the development of the other elements of process safety management in this standard.   a. Mill Blending Area - On or about July 30, 2024, the October 2022 PHA revalidation did not include consultation or participation by hourly employees as written in the employers written program for how they would involve employees in the process.  Failure to include employees that operate and maintain the system can lead to oversite of potential hazards that may lead to the release or exposure of employees to Chlorine.  Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.119 D03 I B

Deleted Other-than-serious 2 instances 10 exposed
Issued
Dec 9, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams (P&ID) were not accurate and did not represent equipment that was existing and was part of the process.  a. Mill Blending Area - On or about July 30, 2024, the piping and instrumentation diagram 4140-PD-01 did not include a 3" piping circuit 3"-PA-0540-03-010-00CS00-N/A, off of PSV 01 between 4140-BL-001 blower and the collection hopper Airlock.  Failure to maintain accurate P&ID's can result in improperly sizing of replacement parts, slowed response and potential exposure to chlorine liquid or gas.  b. Mill Blending Area - On or about July 30, 2024, the piping and instrumentation diagram 4140-PD-01 did not include the piping sizes and information on the piping circuit going to the general suction off of 4"-P-4140-01-003-AA-N/A, 4"-P-4140-01-002-CS-N/A, and 4"-P-4140-01-004-AA-N/A, the P&ID reads ?-P-?-?-?-?-?. Failure to maintain accurate P&ID's can result in improperly sizing of replacement parts, slowed response and potential exposure to chlorine liquid or gas.  Corrected During Inspection
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.119 D03 I F

Other-than-serious 1 instance 10 exposed
Issued
Dec 9, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.119(d)(3)(i)(F): The employer did not include the process safety information the design codes and standards which were employed:  a. Chlorine Room - On or about July 30, 2024, the process safety information pertaining to the design codes and standards employed lacked specificity as to exactly which version of the standard was being used.  Corrected During Inspection
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0