OSHA Inspection: J T INMAN CO., INC.

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of J T INMAN CO., INC. in 31 LARSEN WAY, NORTH ATTLEBORO, MA 02763 (NAICS 339910). OSHA activity number 347654113.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch J T Inman CO., INC. — free Get an email when a new federal OSHA severe-injury report for J T Inman CO., INC. is published. One employer, no account, unsubscribe in one click.
Establishment
J T INMAN CO., INC.
Site address
31 LARSEN WAY
City
NORTH ATTLEBORO
State
MA
ZIP
02763
Mailing
31 LARSEN WAY, NORTH ATTLEBORO, MA 02763
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339910
Employees
15
Ownership type
A

9 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 15 exposed
Issued
Sep 27, 2024
Penalty
Initial $6,452 · Current $2,000 Reduced
OSH ACT of 1970 Section (5)(a)(1):The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that it allowed liquid ammonia to remain in a pressure vessel that was substantially rusted, had 'old' pressure relief valves, and may have been over-pressurized.  Location:  Outdoor ammonia storage vessel located outside the Vibe Room; Pressure relief vent discharge pipe for the annealing furnace.  Instance A:  Pressure relief vessels ( PRV ) on the ammonia tank were not maintained in accordance with CGA G 2.1 0 2014.  Instance B:  An ammonia tank PRV lacked a rain cap or similar device.    Instance C:  The annealing furnace pressure relief discharge vent terminated at below the height of roof.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $6452

1910.111 B03

Other-than-serious Gravity 10 1 instance 15 exposed
Issued
Sep 27, 2024
Penalty
Initial $6,452 · Current $0 Reduced
29 CFR  1910.111(b)(3):  An anhydrous ammonia tank was not labelled or marked in accordance with the requirements of this standard.  Location:  Above ground anhydrous ammonia tank outside Boiler and Vibe Rooms  The anhydrous ammonia tank was not labelled with information about the Code under which it was built; the date of fabrication;  the design pressure; the wall thickness; and the total outside surface area.
Recent events (2)
  • — I (O) $0
  • — Z (S) $6452

1910.111 B05 V

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Sep 27, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.111(b)(5)(v):  Storage areas were not kept free of readily ignitable materials such as waste, weeds, and long dry grass.  Location:  Ammonia Storage Pressure Vessel Outside Vibe Room  A small tree was growing immediately adjacent to the 500 gallon ammonia storage tank.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.111 B11 I

Deleted Serious Gravity 5 1 instance 15 exposed
Issued
Sep 27, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.111(b)(11)(i):Charging of an uninsulated ammonia container exceeded the maximum allowed by OSHA.  Location:  ammonia pressure vessel immediately outside the Vibe Room  On July 31, 2024, 425 gallons of anhydrous ammonia was evacuated from the 500 gallon ammonia tank following an ammonia release from in-plant equipment the previous day.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.111 F06 IV

Other-than-serious Gravity 10 1 instance 15 exposed
Issued
Sep 27, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.111(f)(6)(iv): Valves on ammonia piping were not clearly and legibly marked a metal tag or nameplate identifying their function.  Location:  Ammonia delivery system to the annealing oven.  Ammonia pipe valves, including those where the piping enters the building and at the annealing oven were not marked with their function.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.124 J03

Serious Gravity 10 1 instance 2 exposed
Issued
Sep 27, 2024
Penalty
Initial $6,452 · Current $2,000 Reduced
29 CFR  1910.124(j)(3):  Periodic inspections of all dipping and coating equipment, including covers, drains, overflow piping, and electrical and fire-extinguishing systems were not conducted, and deficiencies were not promptly corrected:  Location:  Vapor degreaser near plating room  The vapor degreaser was not working properly: vapors readily escaped from the degreaser when the cover was removed.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $6452

1910.147 C01

Serious Gravity 10 5 instances 15 exposed
Issued
Sep 27, 2024
Abate by
Dec 2, 2024
Penalty
Initial $6,452 · Current $2,000 Reduced
29 CFR  1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:   Location:  Production Areas  Instance A:  The employer did not ensure that LOTO procedures were developed, documented and used by a contractor cutting piping from the annealing oven.  Instance B:  The employer's LOTO procedures do not involve  removing and controlling plugs or locking out polishers before changing polishing wheels.  Instance C:  The  employer's LOTO procedures do not involve locking out presses prior to performing tasks such as die setting.  Instance D:  The employer has not done annual inspections of its LOTO procedures.  Instance E:   The employer has not provided employees, including employees servicing machinery, with LOTO training.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $6452

1910.147 F02 I

Serious Gravity 10 1 instance 15 exposed
Issued
Sep 27, 2024
Abate by
Dec 2, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.147(f)(2)(i):When outside servicing personnel were engaged in activities in a facility, the onsite employer and the outside employer did not inform each other of their respective lockout or tagout procedures.  Location:  Annealing Oven in large production room  The company did not inform the outside plumber, who was 'isolating' the annealing furnace, of its LOTO procedures.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.217 D09 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 27, 2024
Abate by
Dec 2, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.217(d)(9)(iv):  Safety blocks were not used when mechanical power press die(s) were being adjusted or repaired in the presses.  Location:  Press Area  The employer did not ensure that safety blocks were not used during die setting tasks.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View J T Inman CO., INC.'s full OSHA safety record →