Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RAPID PUMP & METER CO., INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of RAPID PUMP & METER CO., INC. in NEWARK MEADOWLANDS - NEWARK AIRPORT - CITY OF NEWARK PUMP STATION., NEWARK, NJ 07104 (NAICS 811310). OSHA activity number 347660235.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Rapid Pump & Meter CO., INC. — free Get an email when a new federal OSHA severe-injury report for Rapid Pump & Meter CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
NEWARK MEADOWLANDS - NEWARK AIRPORT - CITY OF NEWARK PUMP STATION.
City
NEWARK
State
NJ
ZIP
07104
Mailing
285 STRAIGHT STREET, PATERSON, NJ 07501
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811310
Employees
105
Ownership type
A

4 citations on file for this inspection.

1910.332 B02

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jan 22, 2025
Abate by
Feb 10, 2025
Penalty
Initial $14,895 · Current $6,000 Reduced
29 CFR  1910.332(b)(2):  Employees, who were not qualified persons, were not trained in and familiar with any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety:     (a) Rapid Pump & Meter Co. Inc. - Newark Pump Station - An employee who did not have the training and experience to safely work with electrical equipment was instructed to troubleshoot a pump while  using a 600v meter.  This condition exposed the employee to electrical hazards.    Occurred on July 24th 2024
Recent events (3)
  • — F (O) $6000
  • — C (S) $14895
  • — Z (S) $14895

1910.333 A02

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jan 22, 2025
Abate by
Feb 10, 2025
Penalty
Initial $14,895 · Current $6,000 Reduced
29 CFR  1910.333(a)(2):Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved:  A) Rapid Pump & Meter Co., Inc. - Newark Pump Station - An employee was instructed to troubleshoot a pump while using a 600v meter without proper training and PPE to protect against the energized equipment. This condition exposed employees to electrical hazards.    Occurred on July 24, 2024
Recent events (3)
  • — F (O) $6000
  • — C (S) $14895
  • — Z (S) $14895

1910.334 C01

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jan 22, 2025
Penalty
Initial $14,895 · Current $6,000 Reduced
29 CFR  1910.334(c)(1): Unqualified persons performed testing work on electric circuits or equipment.   a) Rapid Pump & Meter Co., Inc.  at Newark Pump Station - An unqualified employee was assigned to inspect pump 3's electrical panels and switchgear with voltage of 110v, 480v and 4,160v while using a voltage meter make and model Fluke 323, true RMS clamp meter, CAT III 600V, CAT II. This condition exposed the employee to electrical hazards.    Incident occurred on July 24th 2024
Recent events (3)
  • — F (O) $6000
  • — C (S) $14895
  • — Z (S) $14895

1910.334 C03

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jan 22, 2025
Penalty
Initial $14,895 · Current $6,000 Reduced
29 CFR  1910.334(c)(3):Rating of equipment. Test instruments and equipment and their accessories were not rated for the circuits and equipment to which they were connected and were not designed for the environment they were used.  A) a) Rapid Pump & Meter Co., Inc. at Newark Pump Station - An employee used a voltage meter make and model Fluke 323, true RMS clamp meter, CAT III 600V, CAT II to test a control panel that was rated with 4,160 v. This condition exposed the employee to electrical hazards.   Occurred on July 24, 2024
Recent events (3)
  • — F (O) $6000
  • — C (S) $14895
  • — Z (S) $14895

View Rapid Pump & Meter CO., INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347660235.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.