Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TURNER INDUSTRIES GROUP, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TURNER INDUSTRIES GROUP, LLC in 5525 LA-3115, GEISMAR, LA 70734 (NAICS 811310). OSHA activity number 347697062.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Turner Industries Group, LLC — free Get an email when a new federal OSHA severe-injury report for Turner Industries Group, LLC is published. One employer, no account, unsubscribe in one click.
Site address
5525 LA-3115
City
GEISMAR
State
LA
ZIP
70734
Mailing
8687 UNITED PLAZA BLVD, BATON ROUGE, LA 70809
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811310
Employees
120
Ownership type
A

4 citations on file for this inspection.

1910.147 C08

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Nov 26, 2024
Abate by
Dec 12, 2024
Penalty
Initial $16,131 · Current $0 Reduced
29 CFR  1910.147(c)(8): Lockout or tagout was not performed only by the authorized employees performing the servicing or maintenance.   On or about June 7, 2024, in the HFC-245fa Plant, 5th deck of the HFC-245fa process structure at Honeywell Geismar, Turner Industries Group LLC failed to verify that the Lockout/tagout put in place by Honeywell Interenational Inc. was effective in providing administrative controls, engineering controls, and hardware for isolating, securing, or blocking energy sources. The lack of controls contributed to a Hydrofluoric Acid escape that burned an employee.
Recent events (3)
  • — F (S) $0
  • — C (S) $16131
  • — Z (S) $16131

1910.119 H03 I

Deleted Repeat Gravity 10 1 instance 1 exposed
Issued
Nov 26, 2024
Abate by
Dec 16, 2024
Penalty
Initial $80,655 · Current $0 Reduced
29 CFR 1910.119(h)(3)(i): The contract employer did not ensure that each contract employee was trained in the work practices necessary to perform his/her job safely.  On or around June 7, 2024, on the fifth floor of Hydrofluoric Acid Unit 245 at Honeywell Geismar, the employer did not ensure that workers followed safe work practices. The workers were exposed to HF spray and burn hazards when the contract employer did not ensure that the Turner employees had knowledge and training of procedures for valve and gasket change per the job package and work permit.  Turner Industries Group, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.119(h)(3)(iv), which was contained in OSHA inspection number #1575813, citation number 1, item number 3 and was affirmed as a final order on September 7, 2023, with respect to a workplace located at 1300 PPG Drive, Westlake LA, 70669.
Recent events (3)
  • — F (R) $0
  • — C (R) $80655
  • — Z (R) $80655

1910.119 H03 III

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 26, 2024
Abate by
Dec 16, 2024
Penalty
Initial $80,655 · Current $40,328 Reduced
29 CFR  1910.119(h)(3)(iii):The contract employer did not prepare a record which contains the identity of the contract employee, the date of training, and the means used to verify that the employee understood the training.  On or about June 7, 2024, in the HFC-245fa Process Unit, the employer did not effectively implement procedures for properly implementing safe and effective lock-out/ tag-out, specifically block-bleed blind flange side of a closed bleed valve on the D reactor fresh feed system (Valve F105).  Turner Industries Group, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.119(h)(3)(iv), which was contained in OSHA inspection number #1575813, citation number 1, item number 3 and was affirmed as a final order on September 7, 2023, with respect to a workplace located at 1300 PPG Drive, Westlake LA, 70669.
Recent events (3)
  • — F (S) $40327.5
  • — C (R) $80655
  • — Z (R) $80655

1910.119 H03 IV

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Nov 26, 2024
Abate by
Dec 12, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.119(h)(3)(iv): The contract employer did not ensure that each contract worker followed the facility's safe work practices.  On or around June 7, 2024, on the fifth floor of Hydrofluoric Acid Unit 245 at Honeywell Geismar, the employer did not ensure that workers followed safe work practices per the job package and work permit. Turner Industries Group, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.119(h)(3)(iv), which was contained in OSHA inspection number #1575813, citation number 1, item number 3 and was affirmed as a final order on September 7, 2023, with respect to a workplace located at 1300 PPG Drive, Westlake LA, 70669.
Recent events (3)
  • — F (O) $0
  • — C (R) $0
  • — Z (R) $0

View Turner Industries Group, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347697062.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.