CEDARTOWN, GA —
OSHA Inspection: CTS TECHNICAL RESOURCES, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of CTS TECHNICAL RESOURCES, INC. in 408 S 2ND STREET, CEDARTOWN, GA 30125 (NAICS 323120). OSHA activity number 347748881.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CTS TECHNICAL RESOURCES, INC.
- Site address
- 408 S 2ND STREET
- City
- CEDARTOWN
- State
- GA
- ZIP
- 30125
- Mailing
- 408 S 2ND STREET, CEDARTOWN, GA 30125
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323120
- Employees
- 16
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.28 B08 II
- Issued
- Feb 19, 2025
- Abate by
- Mar 19, 2025
- Penalty
- Initial $3,783 · Current $2,251 Reduced
General-duty citation text
29 CFR 1910.28(b)(8)(ii): Employer failed to apply floor markings at least 6 feet (1.8 m) from the edge of the pit in colors that contrast with the surrounding area; or places a warning line at least 6 feet (1.8 m) from the edge of the pit as well as stanchions that are capable of resisting, without tipping over, a force of at least 16 pounds (71 N) applied horizontally against the stanchion at a height of 30 inches (76 cm); or places a combination of floor markings and warning lines at least 6 feet (1.8 m) from the edge of the pit. a) Dipping Pit room: On or about September 11, 2024 and time prior, the employer exposed employees to fall hazards, in that warning lines, floor markings and stanchions were not provided around the dipping pit that measured 79 inches (6ft;7in) in dept.
Recent events (2)
- — I (S) $2250.5
- — Z (S) $3783
1910.147 C01
- Issued
- Feb 19, 2025
- Abate by
- Mar 19, 2025
- Penalty
- Initial $4,729 · Current $2,200 Reduced
General-duty citation text
29 CFR 1910.147(c)(1):The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperable: a) Production floor; On or about, September 11, 2024, and time prior, the employer exposed employees to caught-in hazards, in that the employer did not establish a program for control of hazardous energy for authorized and affected employees who are exposed to LOTO.
Recent events (2)
- — I (S) $2200
- — Z (S) $4729
1910.303 B07 I
- Issued
- Feb 19, 2025
- Abate by
- Mar 19, 2025
- Penalty
- Initial $4,729 · Current $2,200 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment; a. Production floor, On or about September 11, 2024, and times prior, the employer exposed employees to electric shock hazards in that the electrical panel did not have a blanks installed , exposing employees to electric shock while working on the production floor.
Recent events (2)
- — I (S) $2200
- — Z (S) $4729
1910.303 G02 I B
- Issued
- Feb 19, 2025
- Abate by
- Mar 19, 2025
- Penalty
- Initial $4,729 · Current $2,200 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i)(B): By suitable permanent, substantial partitions or screens so arranged so that only qualified persons will have access to the space within reach of the live parts. Any openings in such partitions or screens shall be so sized and located that persons are not likely to come into accidental contact with the live parts or to bring conducting objects into contact with them; a. Production floor, On or about September 11, 2024, and times prior, the employer exposed employees to electric shock hazards in that the several electrical panel cover and junction box covers were removed, exposing employees to electric shock while working on the production floor.
Recent events (2)
- — I (S) $2200
- — Z (S) $4729
1910.178 L02 II
- Issued
- Feb 19, 2025
- Abate by
- Mar 19, 2025
- Penalty
- Initial $531 · Current $400 Reduced
General-duty citation text
29 CFR 1910.178(l)(2)(ii):The employer did not ensure that each operator had successfully completed the training consisting of a combination of formal instruction (e.g., lecture, discussion, interactive computer learning, video tape, written material), practical training (demonstrations performed by the trainer and practical exercises performed by the trainee), and evaluation of the operator's performance in the workplace. a) Production floor: On or about September 11, 2024, and times prior, the employer exposed employees to struck-by hazards, in that powered industrial truck (PIT) training did not include formal training for employees operating the Komatsu 6k LP forklift.
Recent events (2)
- — I (O) $400
- — Z (O) $531
1910.178 L05
- Issued
- Feb 19, 2025
- Abate by
- Mar 19, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(5): Avoidance of duplicative training. Employer failed to verify if an operator has previously received training in a topic specified in paragraph (l)(3) of this section, and such training is appropriate to the truck and working conditions encountered, additional training in that topic is not required if the operator has been evaluated and found competent to operate the truck safely. a) Production floor: On or about September 11, 2024, and times prior, the employer exposed employees to struck-by hazards, in that the employer failed to verify previous powered industrial truck (PIT) training was appropriate to the truck and working condition encountered at his facility (Komatsu 6k LP forklift).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at CTS Technical Resources, INC.
View CTS Technical Resources, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 323120)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347748881.