NORWOOD, MA —
OSHA Inspection: HOME MARKET FOODS, INC.
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of HOME MARKET FOODS, INC. in 140 MORGAN DRIVE, NORWOOD, MA 02062 (NAICS 311412). OSHA activity number 347756397.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HOME MARKET FOODS, INC.
- Site address
- 140 MORGAN DRIVE
- City
- NORWOOD
- State
- MA
- ZIP
- 02062
- Mailing
- 140 MORGAN DRIVE, NORWOOD, MA 02062
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311412
- Employees
- 585
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.119 J02
- Issued
- Feb 27, 2025
- Abate by
- Apr 17, 2025
- Penalty
- Initial $16,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): Employer did not establish or implement written procedures to maintain the on-going integrity of process equipment: Ammonia Refrigeration Machine (Engine) Room: Employer did not develop written procedures to maintain the on-going integrity of the piping system of the employer's ammonia refrigeration equipment inside the ammonia machine room: a) On or about September 3, 2024, a drain valve and drain plug for a recirculating pump for the low pressure receiver (LPR) vessel leaked approximately 721 pounds of ammonia refrigerant when the drain valve and drain plug were not effectively closed. b) On or about November 17, 2024, a purge line pipe for the LPR began leaking ammonia refrigerant when the purge line pipe failed.
Recent events (3)
- — F (S) $0
- — C (S) $16550
- — Z (S) $16550
1910.119 J04 IV
- Issued
- Feb 27, 2025
- Abate by
- Apr 17, 2025
- Penalty
- Initial $16,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(4)(iv): Documentation of each inspection and test that had been performed on process equipment did not identify the date of the inspection or test, the name of the person who performed the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test performed, and the results of the inspection or test: Ammonia Refrigeration Machine (Engine) Room: Documentation of each inspection and test that had been performed on components of the piping system of the employer's ammonia refrigeration system did not include the following information: a) On or about September 3, 2024, documents of each inspection and test performed for a drain valve and drain plug for a recirculating pump for the low pressure receiver (LPR) vessel did not include all information listed in ANSI/IIAR (American National Safety Institute/International Institute of Ammonia Refrigeration) IIAR 6 2019 edition 5.1.1.3 including, but not limited to, serial number or other identifier of the equipment on which the inspection or test was performed. b) On or about November 17, 2024, documents of each inspection and test performed for a purge line pipe for the low pressure receiver (LPR) vessel did not include all information listed in ANSI/IIAR (American National Safety Institute/International Institute of Ammonia Refrigeration) IIAR 6 2019 edition 5.1.1.3 including, but not limited to, serial number or other identifier of the equipment on which the inspection or test was performed.
Recent events (3)
- — F (S) $0
- — C (S) $16550
- — Z (S) $16550
1910.119 J05
- Issued
- Feb 27, 2025
- Abate by
- Apr 17, 2025
- Penalty
- Initial $16,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(5): Employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) in a safe and timely manner when necessary means were taken to assure safe operation: Establishment: Employer did not correct deficiencies in the following ammonia refrigeration equipment that were outside acceptable limits as per employer's process safety information in a timely manner to assure safe operation: a) On or about September 3, 2024, a drain valve and drain plug for a recirculating pump for the low pressure receiver (LPR) vessel leaked approximately 721 pounds of ammonia refrigerant when the drain valve and drain plug were not effectively closed. b) On or about November 17, 2024, a purge line pipe for the LPR began leaking ammonia refrigerant when the purge line pipe failed.
Recent events (3)
- — F (S) $0
- — C (S) $16550
- — Z (S) $16550
1910.119 D03 II
- Issued
- Feb 27, 2025
- Abate by
- Sep 5, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(d)(3)(ii): Employer did not document that equipment complies with recognized and generally accepted good engineering practices. Ammonia Refrigeration Machine (Engine) Room: On or about September 3, 2024, piping system equipment/components such as drain valves for the recirculating pump package of the low pressure receiver (LPR) vessel did not have unique labels on which the inspections or tests were performed in accordance with ANSI/IIAR (American National Safety Institute/International Institute of Ammonia Refrigeration) IIAR 2 2021 edition, 5.14.3 and ANSI/IIAR 3 2022 edition, Chapter 8.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at Home Market Foods, INC.
View Home Market Foods, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311412)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347756397.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.