Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GEORGIA-PACIFIC BROADWAY LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of GEORGIA-PACIFIC BROADWAY LLC in 1919 S. BROADWAY, GREEN BAY, WI 54304 (NAICS 322291). OSHA activity number 347865180.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Georgia-Pacific Broadway LLC — free Get an email when a new federal OSHA severe-injury report for Georgia-Pacific Broadway LLC is published. One employer, no account, unsubscribe in one click.
Site address
1919 S. BROADWAY
City
GREEN BAY
State
WI
ZIP
54304
Mailing
1919 S. BROADWAY, GREEN BAY, WI 54304
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322291
Employees
950
Ownership type
A

5 citations on file for this inspection.

1910.22 A01

Other-than-serious Gravity 1 1 instance 16 exposed
Issued
Dec 6, 2024
Penalty
Initial $6,464 · Current $3,856 Reduced
29 CFR 1910.22(a)(1):  All places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition.  On or about October 30, 2024 and thereafter, at an establishment located at 1919 South Broadway, Green Bay, Wisconsin; on the Drive Side Yankee Mezzanine Level for Paper Machine 9, extension cord(s), power cord(s), and water hose(s) were on the floor where employees were conducting their rounds exposing the employees to slip and trip hazards.
Recent events (2)
  • — I (O) $3856.4
  • — Z (S) $6464

1910.261 K11

Serious Gravity 5 4 instances 16 exposed
Issued
Dec 6, 2024
Abate by
Jan 7, 2025
Penalty
Initial $10,775 · Current $6,465 Reduced
29 CFR 1910.261(k)(11):  Steam and hot-water pipes. All exposed steam and hot-water pipes within 7 feet of the floor or working platform or within 15 inches measured horizontally from stairways, ramps, or fixed ladders shall be covered with an insulating material or guarded in such manner as to prevent contact.  On or about October 30, 2024 and thereafter, at an establishment located at 1919 South Broadway, Green Bay, Wisconsin;   (a)  Paper Machine 9 Dry Side Mezzanine Level, the 35-pound steam pipe at the connection flange for the steam shower had an exposed steam pipe without insulating material exposing employees to thermal burns.   (b)  Paper Machine 9 Dry Side Mezzanine Level, the 35-pound steam pipe for Steam Shower, next to 35-pound steam supply to steam box bleed off valve had an exposed steam pipe without insulating material exposing employees to thermal burns.  (c)  Paper Machine 9 Drive Side Yankee Mezzanine Level, the 400-pound steam flange and bolts on the drive side mezzanine by the step down had an exposed steam pipe without insulating material exposing employees to thermal burns.  (d)  Paper Machine 9 Drive Side Yankee Mezzanine Level, the 400-pound steam pipe on the drive side mezzanine labeled "1-009 -003 Pressure" had an exposed steam pipe without insulating material exposing employees to thermal burns.
Recent events (2)
  • — I (S) $6465
  • — Z (S) $10775

1910.334 A02 I

Serious Gravity 10 2 instances 16 exposed
Issued
Dec 6, 2024
Penalty
Initial $16,131 · Current $9,679 Reduced
29 CFR 1910.334(a)(2)(i):  Portable cord and plug connected equipment and flexible cord sets (extension cords) shall be visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket). Cord and plug connected equipment and flexible cord sets (extension cords) which remain connected once they are put in place and are not exposed to damage need not be visually inspected until they are relocated.  On or about October 30, 2024 and thereafter, at an establishment located at 1919 South Broadway, Green Bay, Wisconsin; on the Drive Side Yankee Mezzanine Level for Paper Machine 9, the extension cord and Dayton fan electrical cord were not visually inspected before use on any shift for external defects such as damaged female plug and male prongs exposing employees to electrical shock and fire hazards.
Recent events (2)
  • — I (S) $9678.6
  • — Z (S) $16131

1910.334 A02 II

Serious Gravity 10 2 instances 16 exposed
Issued
Dec 6, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made.  On or about October 30, 2024 and thereafter, at an establishment located at 1919 South Broadway, Green Bay, Wisconsin; on the Drive Side Yankee Mezzanine Level for Paper Machine 9, the extension cord and Dayton fan electrical cord were not removed from service when damaged causing in sparking exposing employees to electrical shock and fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.242 B

Other-than-serious 1 instance 16 exposed
Issued
Dec 6, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.242(b):  Compressed air used for cleaning. Compressed air shall not be used for cleaning purposes except where reduced to less than 30 p.s.i. and then only with effective chip guarding and personal protective equipment.  On or about October 30, 2024 and thereafter, at an establishment located at 1919 South Broadway, Green Bay, Wisconsin; Paper Machine 9 Yankee Dryer Mezzanine Tender Side, the extended air nozzle attached to the red hose used to blow down and clean around the Yankee dryer had a pressure greater than 30 psi exposing employees to injuries related to compressed air entering the body such as swelling, severe pain, or air embolism.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Georgia-Pacific Broadway LLC's full OSHA safety record →