Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: INTERTEK USA INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of INTERTEK USA INC in 1114 SEACO AVE., DEER PARK, TX 77536 (NAICS 541380). OSHA activity number 347882102.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Intertek USA INC — free Get an email when a new federal OSHA severe-injury report for Intertek USA INC is published. One employer, no account, unsubscribe in one click.
Establishment
INTERTEK USA INC
Site address
1114 SEACO AVE.
City
DEER PARK
State
TX
ZIP
77536
Mailing
1114 SEACO AVE., DEER PARK, TX 77536
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541380
Employees
140
Ownership type
A

2 citations on file for this inspection.

1910.307 B

Serious Gravity 5 1 instance 4 exposed
Issued
Dec 19, 2024
Abate by
Jan 16, 2025
Penalty
Initial $7,835 · Current $4,701 Reduced
29 CFR 1910.307(b): Areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007, were not properly documented:  a)  On or about November 9, 2024, at the testing laboratory, hazardous (classified) locations, such as areas subject to the potential release of flammable liquified petroleum gas (LPG), were not properly documented.
Recent events (2)
  • — I (S) $4701
  • — Z (S) $7835

1910.307 C

Serious Gravity 5 1 instance 4 exposed
Issued
Dec 19, 2024
Abate by
Jan 16, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.307(c):  Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:  a) On or about November 9, 2024, at the testing laboratory, a Dell monitor and an electrical outlet located next to the gas pod of an EST Analytical instrument was not approved for a classified location. Employees perform a test method ASTM D6667 on this instrument, which subjects to the potential release of flammable liquified petroleum gas (LPG).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Intertek USA INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347882102.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.