Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PENNSYLVANIA AMERICAN WATER COMPANY

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of PENNSYLVANIA AMERICAN WATER COMPANY in 203 ONEIDA VALLEY ROAD, BUTLER, PA 16001 (NAICS 221310). OSHA activity number 347896466.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pennsylvania American Water Company — free Get an email when a new federal OSHA severe-injury report for Pennsylvania American Water Company is published. One employer, no account, unsubscribe in one click.
Site address
203 ONEIDA VALLEY ROAD
City
BUTLER
State
PA
ZIP
16001
Mailing
203 ONEIDA VALLEY ROAD, BUTLER, PA 16001
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221310
Employees
11
Ownership type
A

2 citations on file for this inspection.

1910.119 J02

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
May 16, 2025
Abate by
Jul 7, 2025
Penalty
Initial $11,823 · Current $0 Reduced
29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment:  a) In the Chlorine Storage Room, on or about November 21, 2024 - The employer did not establish written procedures to maintain the on-going integrity of Halogen Valve Eclipse Actuators.    b) In the Chlorine Storage Room, on or about November 21, 2024 - The employer did not establish written procedures to maintain the on-going integrity of the Wallace & Tiernan Vacuum Regulators.  c) In the Chlorine Storage and Feed Rooms, on or about November 21, 2024 - The employer did not establish written procedures to maintain the on-going integrity of the Wallace & Tiernan Acutec 35 Gas Detection System.  d)  In the Chlorine Storage and Feed Rooms, on or about November 21, 2024 - The employer did not establish written procedures to maintain the on-going integrity of the chlorine piping.  Failure to develop inspection procedures that establish written procedures to maintain the on-going integrity of process equipment can expose employees to corrosive, toxic, and oxidizing hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $11823
  • — Z (S) $11823

1910.119 J04 III

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
May 16, 2025
Abate by
Jul 7, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience:   a) In the Chlorine Storage Room, on or about November 21, 2024 - The employer did not test cycle at least once per week the Halogen Valve Eclipse Actuator's actuator system. The actuator's Installation, Operations and Maintenance Manual instructs users to test cycle the actuator system at least once per week to reduce the potential for fouling.   b) In the Chlorine Storage Room, on or about November 21, 2024 - The employer did not perform periodic cleaning and periodic preventative maintenance of the Wallace & Tiernan Vacuum Regulators consistent with the regulator instruction book. The book instructs users to perform periodic cleaning after 12,000 pounds of gas has been feed to ensure that elements of the regulator is free of contaminants. The book instructs users to perform periodic preventative maintenance to recondition the regulator at one-year intervals.  Failure to perform inspections and tests of process equipment consistent with manufacturers' frequency recommendations can expose employees to corrosive, toxic, and oxidizing hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

View Pennsylvania American Water Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347896466.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.