SAN ANTONIO, TX —
OSHA Inspection: THE LEVY COMPANY
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of THE LEVY COMPANY in 1002 EDWARDS BURBANK HS- NEW AUDITORIUM, SAN ANTONIO, TX 78204 (NAICS 237310). OSHA activity number 347901373.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE LEVY COMPANY
- Site address
- 1002 EDWARDS BURBANK HS- NEW AUDITORIUM
- City
- SAN ANTONIO
- State
- TX
- ZIP
- 78204
- Mailing
- 16294 I-35, SELMA, TX 78154
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237310
- Employees
- 3
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.403 I02 III
- Issued
- Apr 21, 2025
- Penalty
- Initial $12,768 · Current $10,000 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(iii): Entrances to rooms and other guarded locations containing exposed live parts operating at 600 volts, nominal, or less were not marked with conspicuous warning signs forbidding unqualified persons to enter: On or about November 20, 2024, the entrance to the electrical room was not adequately marked with warning signage prior to electrical work being conducted.
Recent events (2)
- — I (S) $10000
- — Z (S) $12768
1926.416 A03
- Issued
- Apr 21, 2025
- Abate by
- May 9, 2025
- Penalty
- Initial $14,895 · Current $11,000 Reduced
General-duty citation text
29 CFR 1926.416(a)(3): Before work began the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring a person, tool, or machine into physical or electrical contact with the energized electric power circuit: On or about November 20, 2024, the employer did not determine whether an electric powered circuit was deenergized prior to conducting electrical work.
Recent events (2)
- — I (S) $11000
- — Z (S) $14895
1926.417 A
- Issued
- Apr 21, 2025
- Abate by
- May 9, 2025
- Penalty
- Initial $14,895 · Current $11,000 Reduced
General-duty citation text
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged: On or about November 20, 2024, the employer did not tag individual circuit breakers that were to be deactivated prior to beginning electrical work.
Recent events (2)
- — I (S) $11000
- — Z (S) $14895
1904.39 A02
- Issued
- Apr 21, 2025
- Penalty
- Initial $10,641 · Current $0 Reduced
General-duty citation text
29 CFR 1904.39(a)(2):The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye. On or about November 20, 2024, the employer did not report to OSHA a work-related injury requiring hospitalization of a worker.
Recent events (2)
- — I (O) $0
- — Z (O) $10641
More inspections at The Levy Company
View The Levy Company's full OSHA safety record →
More inspections in this industry (NAICS 237310)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347901373.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.